Different transformers

CCR, fixture, sign and approach-light: four transformers that work on the same principle but differ in where they sit, what they feed and what happens when they fail.

FOUR TRANSFORMERS · SAME PRINCIPLE, DIFFERENT JOBS CCR TRANSFORMER at the power end CCR CABINET SUPPLY TO LOOP builds the loop voltage one per CCR, rated in kW a fault hits the whole circuit FIXTURE ISOLATING one light on the loop SERIES LOOP TO LAMP isolates one light below ground, in a can or pit open primary can open loop SIGN TRANSFORMER one sign on the loop SERIES LOOP TO SIGN feeds one sign only sized to the sign load plug-in sealed connectors APPROACH-LIGHT one light on a stem SERIES LOOP TO LAMP one per light, in a can lead up the frangible stem failed lamp darkens one light
Primary / series loop
Secondary / to the load
Light or sign
The Fact IEC 61823

An AGL series circuit uses transformers at both ends. At the power end the CCR transformer feeds the whole circuit. Out in the field, isolating transformers connect each light or sign to the loop. Three common field types are the fixture transformer, the sign transformer and the approach-light transformer. They differ in what they feed, where they sit, how they are rated, and what a fault does.

In every case the transformer keeps the load electrically apart from the loop. In the field types the primary is in series and carries the circuit current, and the secondary feeds one load through a short lead, so a lamp or sign fault normally leaves the loop closed. The exception to watch is an open primary, which can open the circuit. The CCR transformer is different in scale: it supplies the entire circuit, so its failure takes out the whole circuit.

CCR transformer

One per circuit, at the power end. It isolates the field cable from the supply and builds the voltage the loop needs, rated in kW.

Isolating transformers

Many per circuit, out in the field. Each connects one load to the series loop and keeps it electrically apart, rated in watts.

AspectCCR transformerFixture isolatingSign transformerApproach-light
DoesIsolates the field cable from the supply and builds the voltage the loop needs for its set currentConnects one light to the series loop and keeps its lamp or LED unit isolatedConnects one sign to the series loop and keeps the sign isolatedConnects one approach light to the series loop and keeps its lamp isolated
WhereInside the CCR, at the power end of the circuitBelow ground in a base can or pit beside the lightAt or near the sign, in its base or a nearby pit, as designedBelow ground in a can beside the base of the stem
Primary sideThe supply, for example 230 V single-phase or 415 V three-phaseIn series with the loop; carries the circuit currentIn series with the loop; carries the circuit currentThe series loop passes through the can into the primary
Secondary sideTo the series circuit; a tap sets the most voltage it can developTo the lamp or LED unit by a short leadTo one sign through a short cableA short lead up the frangible stem to the lamp
RatingIn kW, set by the load on the circuitA set size in watts, matched to the lamp or LED loadA set size in watts, covering the sign loadA set size in watts, matched to the lamp load
How manyOne per CCRNormally one per lightOne per signOne per light
If it failsThe whole circuit loses its supplyA lamp or secondary fault darkens that light; an open primary can open the circuitA sign or secondary fault leaves the loop closed; an open primary can open the circuitA failed lamp darkens only that light; an open primary can open the circuit
Watch pointsTap setting and headroom; never open a live series circuitRating, sealed connectors, insulation, water in the can or pitRating against the sign load, connectors, secondary cableRating, connectors, can seal and drainage, the stem lead
Schematic — transformers differ between products and designs. Ratings, ratios, tolerances, insulation levels and locations depend on the standard (IEC / FAA), the airport’s circuit design and the manufacturer’s data sheet. Isolate and lock out the circuit before working on any transformer.

What to check on transformers

Rating on the nameplate

Check the rating against the load it feeds and the primary against the circuit current, from the nameplate and the design.

Connectors and seals

Check the sealed connectors are intact, correctly mated and dry. A damaged or wet connector is a common cause of faults.

Insulation

Test insulation to the limits in the procedure and record the value, so a falling trend can be seen over the years.

Can or pit

Keep the can or pit dry, drained and sealed. Water in the can attacks connectors and leads long before the transformer fails.

Secondary lead and load

Check the secondary lead and the load match the design, and that the lead is undamaged where it runs up a stem or into a sign.

Isolate before work

Isolate and lock out the circuit first. Unplugging a primary connector opens the loop, and the secondary side should be treated as live.

Entry 5 · Different taxiway fixtures Entry 7 · Different connectors

Frequently Asked Questions

Q1What are the main transformers in an AGL series circuit?

Four common ones are the CCR transformer, the fixture isolating transformer, the sign transformer and the approach-light transformer. The CCR transformer sits at the power end and feeds the whole circuit. The other three are isolating transformers out in the field, each connecting one load to the series loop.

Q2What does the CCR transformer do?

It sits between the thyristor stage and the series circuit. It isolates the field cable from the supply and builds the voltage the loop needs to carry the set current. A secondary tap sets the most voltage the CCR can develop, so it also sets the headroom for the circuit.

Q3What does an isolating transformer do?

It connects one light or sign to the series loop. Its primary is in series with the loop and carries the circuit current, while its secondary feeds only that load through a short lead. The two sides are kept electrically apart, so a lamp or sign fault does not stop the rest of the circuit.

Q4How is a sign transformer different from a fixture transformer?

The principle is the same, since both are series isolating transformers. The difference is the load and the place. A sign transformer feeds one sign through a short cable and is rated for the sign load, which can be larger for a bigger or double-faced sign. A fixture transformer feeds one light, usually from a can or pit beside it.

Q5Why is the approach-light transformer arranged differently?

Approach lights stand on frangible stems, so the transformer is kept below ground in a can beside the stem. The loop passes through the can, and a short secondary lead runs up the stem to the lamp. This keeps the stem light and protects the transformer from weather and traffic.

Q6What limits and requirements apply?

Ratings, ratios, tolerances and insulation levels come from the standard, such as IEC 61823 or the FAA specifications, the airport's circuit design and the manufacturer's data sheet. Always use the requirements for your site rather than a generic list, and isolate and lock out the circuit before working on any transformer.

Precision AGL Academy

See It. Understand It. Then Learn How to Engineer It.

Recognising an AGL system visually is the first step. The next step is knowing how to design, install, test, commission and maintain them correctly.

Build Practical AGL Engineering Skills

Go deeper with structured training from Precision AGL Academy, covering:

AGL Fundamentals Design & Electrical Engineering Approach Lighting Photometry Installation & Commissioning Maintenance & Troubleshooting

Learn how each light, sign and circuit works as part of a complete airport lighting system, not just as an isolated diagram.

See. Understand. Apply. Engineer.