Different CCR technologies

Thyristor, saturable reactor, moving coil and switch-mode: four ways to hold one constant current in a series circuit, differing in control method, moving parts and waveform.

FOUR CCR TECHNOLOGIES · SAME CURRENT, DIFFERENT METHODS THYRISTOR (SCR) phase-angle control FIRE PHASE-ANGLE FIRING fires later for lower current closed loop on output current chopped waveform: true-RMS meter SATURABLE REACTOR magnetic control DC CONTROL DC SETS THE OUTPUT control current sets the output no switching of the supply older design, still in service MOVING COIL constant-current transformer FIXED MOVES COIL POSITION SETS CURRENT secondary coil moves mechanical parts to inspect output close to supply waveform SWITCH-MODE high-frequency switching FILTER PULSE WIDTH SETS OUTPUT pulses filtered to the output newer solid-state design follow the maker's data
Power / supply path
Control path
The Fact IEC 61822

Every constant current regulator does the same job: it holds a fixed current in a series lighting circuit, and the selected intensity step sets that current. What differs is the power stage. A thyristor CCR fires a pair of thyristors at a chosen angle. A saturable reactor is controlled by a DC winding. A moving-coil regulator changes the coupling by moving a coil. A switch-mode regulator switches at high frequency and filters the result. Other designs, such as the ferroresonant regulator, are also widely used.

In thyristor, switch-mode and saturable-reactor designs the loop that keeps the current right is the same idea: measure the output, compare it with the step, and correct. A moving-coil regulator holds the current largely through the magnetic balance of its coil rather than electronic feedback, as the design provides. The difference shows up in the maintenance. A moving-coil type has moving parts to inspect, a thyristor type has a chopped waveform that needs a true-RMS meter, and every type has heat to manage. Terms and designs vary between makers, so check the data for the unit in front of you.

Solid-state stages

Thyristor and switch-mode regulators use electronic switching in the power stage. They have no moving power parts but need cooling and a suitable meter.

Magnetic and mechanical stages

Saturable-reactor and moving-coil regulators control the current through magnetic coupling. The moving-coil type adds mechanical parts to inspect.

AspectThyristorSaturable reactorMoving coilSwitch-mode
Control methodAnti-parallel thyristors fired at a set angle in each half-cycleA DC control current in a reactor winding changes how much the reactor passesA secondary coil moves relative to the primary, changing the couplingFast switching of the supply with the pulse width varied, then filtered
How it holds currentA current sensor feeds the control board, which adjusts the firing angle to hold the set stepThe control current is adjusted to hold the set step, as the design providesThe coil position is set for each step, as the design providesA current sensor feeds the controller, which adjusts the pulse width to hold the set step
Moving partsNone in the power stage; a fan may cool itNone in the power pathYes: the coil and its driveNone in the power stage; a fan may cool it
Output waveformChopped; measure with a true-RMS meterCheck the maker’s data for the unitClose to the supply waveformFiltered; check the maker’s data for the unit
Typical positionCommon in modern CCRsOlder designs, still in service on some airfieldsOlder mechanical designs, still in service on some airfieldsNewer solid-state designs
Heat and coolingPower stage and transformer heat removed by heatsink and fanReactor and transformer heat; check the maker’s cooling dataWinding heat and the drive; check the maker’s cooling dataSwitching devices and filter heat removed by heatsink and fan
Watch pointsFiring and control board, thyristors, fan, filter, protection settingsControl winding, reactor condition, step accuracyCoil drive and travel, wear, step accuracy, lubrication as the maker requiresSwitching stage, filter, fan, control board, protection settings
Schematic — designs differ between makers, and the four types shown are not the only ones: the ferroresonant regulator is another widely used design. Ratings, accuracy, protection and test limits depend on the standard (IEC / FAA), the airport’s circuit design and the manufacturer’s data. Never open a live series circuit; isolate, lock out and prove the circuit dead first.

What to check on CCRs

Output current at each step

Measure the output at every step with a meter suited to the waveform, and compare it with the setting.

Waveform and meter

A chopped waveform needs a true-RMS meter. Check the maker’s data for the meter and method for the type in use.

Moving parts and wear

On a moving-coil type, check coil travel, drive and wear. Solid-state types have no moving power-stage parts but a fan to check.

Heat and cooling

Check fans, filters, heatsinks and ventilation. Heat is the common enemy of every regulator.

Protection and alarms

Check overcurrent and open-circuit protection, and that alarms reach the control system, as the standard requires.

Isolate before work

Never open a live series circuit. Isolate, lock out and prove the circuit dead before work.

Entry 10 · Different PAPI systems Entry 12 · Runway fixture selection

Frequently Asked Questions

Q1What do all CCR technologies have in common?

Every constant current regulator holds a fixed current in a series lighting circuit, and the selected intensity step sets that current. They differ in how they do it: by switching the supply with thyristors, by controlling a saturable reactor, by moving a coil in a transformer, or by high-frequency switching.

Q2How does a thyristor CCR hold the current?

A pair of anti-parallel thyristors is fired at a chosen angle in each half-cycle. A later firing angle passes less of the waveform and lowers the output. A current sensor on the output feeds the control board, which adjusts the firing angle to hold the set step. The output waveform is chopped, so measure it with a true-RMS meter.

Q3What is a moving-coil CCR?

It is a constant-current transformer whose secondary coil can move relative to the primary. Moving the coil changes the coupling between them, which changes the current delivered to the circuit. It is a mechanical design, so it has moving parts that need inspection.

Q4Which technology should I choose?

That depends on the airport's circuit, the standard, the maker's data and the maintenance practice on site. Compare control method, moving parts, waveform, efficiency, size and spares, and follow the specification for the project rather than a generic rule.

Q5What limits and requirements apply?

Ratings, accuracy, protection and test limits come from the standard, such as IEC 61822 or FAA AC 150/5345-10, and from the manufacturer's data for the unit. Use the requirements for your site, and never open a live series circuit; isolate, lock out and prove the circuit dead first.

Precision AGL Academy

See It. Understand It. Then Learn How to Engineer It.

Recognising an AGL system visually is the first step. The next step is knowing how to design, install, test, commission and maintain them correctly.

Build Practical AGL Engineering Skills

Go deeper with structured training from Precision AGL Academy, covering:

AGL Fundamentals Design & Electrical Engineering Approach Lighting Photometry Installation & Commissioning Maintenance & Troubleshooting

Learn how each light, sign and circuit works as part of a complete airport lighting system, not just as an isolated diagram.

See. Understand. Apply. Engineer.