Different connectors

Primary, secondary, in-line and CCR-end: four connection points on one series circuit that look alike but differ in what they carry, where they sit and what a fault does.

FOUR CONNECTION POINTS · SAME CIRCUIT, DIFFERENT ROLES PRIMARY CONNECTOR in the series loop IN OUT FROM LOOP TO LOOP in the loop, full current two per transformer, in / out a bad joint can stop the circuit SECONDARY CONNECTOR on the isolated side SECONDARY TO LIGHT to one fitting only one per light or sign a bad joint darkens one fitting IN-LINE CABLE JOINT joins cable lengths JOINT CABLE CABLE joins lengths of primary cable made on site, sealed in ground a bad joint can stop the circuit CCR-END TERMINATION at the power end CCR CCR OUTPUT TO FIELD cable lands on CCR output a terminated end, not plug-in a poor end affects the circuit
Primary / series loop
Secondary / to the light
Connector, joint or light
The Fact FAA L-823

A series circuit is only as sound as its joints. Wherever cable meets a transformer, another cable or the regulator, there is a connection point, and they are not all equal. The primary connector and the in-line cable joint sit in the loop and carry the full circuit current. The secondary connector sits on the isolated side and serves one fitting. The CCR-end termination is where the field cable lands on the regulator.

That is why the same-looking plug matters differently. A bad joint in the loop can stop every light on the circuit, and a loose or corroded one adds resistance, heats up and can arc. A bad secondary joint normally leaves the loop closed and darkens only that fitting. Whatever the type, the common enemy is water.

Joints in the loop

Primary connectors, in-line joints and the CCR-end termination carry the full loop current. One poor joint can affect the whole circuit.

Joint on the secondary

The secondary connector serves one light or sign on the isolated side. A fault stays local to that fitting.

AspectPrimary connectorSecondary connectorIn-line cable jointCCR-end termination
DoesJoins a transformer’s primary lead to the loop cable, in and out, so the series current passes through itJoins a transformer’s secondary lead to the lead to one light or signJoins two lengths of primary cable into one continuous runLands the field cable on the CCR output so the loop can leave the regulator
WhereIn a base can or transformer pit beside the light or signIn the same can or pit, between the transformer and the fittingAlong the cable route, in a pit, handhole or trench as designedInside the CCR cabinet at the power end
CarriesThe full loop current, the same as every other joint in the circuitThe current of one fitting only, on the isolated sideThe full loop currentThe full loop current, leaving and returning
Made asA sealed plug-and-receptacle joint that can be separated for test or replacementA sealed plug-and-receptacle joint, often keyed and sized differently from the primaryA joint made on site and sealed to the maker’s method; not meant to be separatedA terminated cable end, secured at the terminals as the CCR maker specifies
How manyTwo per transformer (in and out)One per light or signAs many as the cable route needsNormally one pair per circuit
If it failsAn open joint can break the loop for every light; a poor contact heats up and can arcThat one light or sign dims or goes dark; the loop stays closedAn open or wet joint can stop the circuit or cause an earth faultThe circuit can lose its output or show a fault at the CCR
Watch pointsSeating, seals, contact condition, insulation resistance, water in the canSeating, seals, flicker or dimming, water leakageJoint quality at install, depth, drainage, insulation-resistance trendTerminal tightness, cable end condition, labelling, isolation before touching
Schematic — connector designs differ between makers and sites. Types, ratings, sealing methods and test limits depend on the standard (FAA / IEC), the airport’s circuit design and the manufacturer’s instructions. Never separate a primary connector on an energised circuit; isolate, lock out and prove the circuit dead before touching any connector.

What to check on connectors

Match the connector to the job

Check the connector type and size against the design and the maker’s data. Primary and secondary connectors are not interchangeable.

Seating and locking

Check each connector is fully mated, keyed and locked as the maker requires. A half-seated joint is a common cause of heating.

Seals and water

Check boots, seals and the can or pit are intact and dry. Water in a joint lowers insulation resistance long before it opens.

Insulation and continuity

Test to the limits in the procedure and record the values, so a falling trend shows up over the years.

Heat and discolouration

Look for browning, melting or a burnt smell at a joint. A high-resistance contact heats up and can arc.

Isolate before work

Never separate a primary connector on an energised circuit. Isolate, lock out and prove the circuit dead, and treat every lead as live.

Entry 6 · Different transformers Entry 8 · Different cables

Frequently Asked Questions

Q1What are the main connection points on an AGL series circuit?

Four common ones are the primary connector, the secondary connector, the in-line cable joint and the CCR-end termination. The primary connector and the in-line joint sit in the series loop. The secondary connector sits on the isolated side of a transformer and serves one fitting. The CCR-end termination is where the field cable lands on the regulator.

Q2What is the difference between a primary and a secondary connector?

A primary connector joins a transformer's primary lead to the loop cable, so it carries the full circuit current and a fault can stop every light on the circuit. A secondary connector joins the transformer's secondary lead to one fitting, so a fault normally affects that one light or sign only.

Q3Why does a primary connector matter more than a secondary one?

Because the loop is a series circuit, current passes through every primary connector in turn. An open joint breaks the loop for everything on it, and a loose or corroded contact adds resistance, heats up and can arc. The secondary side is isolated, so its faults stay local.

Q4Is an in-line cable joint the same as a connector?

No. A connector is a plug-and-receptacle joint that can be separated for testing or replacement. An in-line joint permanently joins two lengths of primary cable, usually made on site and sealed in the ground. Both carry loop current, so both are weak points to inspect and test.

Q5What limits and requirements apply?

Connector types, ratings, sealing methods and test limits come from the standard, such as the FAA L-823 specification or the relevant IEC requirements, the airport's design and the manufacturer's instructions. Use the requirements for your site, and never separate a primary connector on an energised circuit; isolate, lock out and prove the circuit dead first.

Precision AGL Academy

See It. Understand It. Then Learn How to Engineer It.

Recognising an AGL system visually is the first step. The next step is knowing how to design, install, test, commission and maintain them correctly.