What is a sign transformer?

The link between the series loop and one sign. Its primary sits in the loop, its secondary feeds the sign, and the two are kept electrically apart.

SIGN TRANSFORMER 1 PRIMARY IN THE LOOP, SECONDARY TO ONE SIGN FROM LOOP TO NEXT LIGHT PRIMARY SECONDARY MAGNETIC COUPLING NO DIRECT PATH Commonly a 1:1 current ratio, for example 6.6 A : 6.6 A. 2 RATING MUST COVER THE SIGN LOAD TRANSFORMER RATING SIGN LOAD (LED + DRIVER) SPARE CAPACITY A heavier sign needs a larger rating from the standard sizes. Wattages are illustrative. Sizes and limits vary by standard. 3 WHAT THE SIGN TRANSFORMER DOES Isolates Keeps the sign apart from the loop Secondary has no direct link to primary Keeps the loop Primary stays in the series chain Loop stays closed if the sign is off Sized to load Rating covers the sign load CCR carries the sum of all loads Unplugging a primary connector opens the loop. Isolate the circuit and make it safe first. SCHEMATIC · WINDINGS AND WATTAGES ILLUSTRATIVE · NOT TO SCALE
primary, in the loop
secondary, to the sign
sign load
The Fact Circuit Practice

A sign cannot be wired straight into a series loop. The loop carries a constant current at high voltage, and the sign needs a supply of its own. The isolation transformer between them solves both: it passes the power across and keeps the two sides apart.

1Primary in the loop

The transformer's primary winding is a link in the series loop, so the circuit current flows through it in turn with every other light. Its leads are joined to the loop through sealed connectors, so the transformer can be disconnected, tested or replaced without re-jointing the main cable.

2Secondary to one sign

The secondary winding feeds only this sign, through a short cable. Energy crosses magnetically, with no direct electrical path between the windings, so the sign is isolated from the loop. If the sign or its secondary cable is disconnected, the primary loop stays closed and the other lights stay on.

3Sized to the sign

Transformers are made in set rated powers, and the sign's load, its LED module and driver, should sit within the rating chosen. A larger or double-faced sign draws more. Every sign's load also adds to the circuit total that the CCR has to supply. Isolate and make the circuit safe under site procedures before any work, because unplugging a primary connector opens the loop and the secondary should be treated as live. A sign left with an open secondary raises the primary voltage and heats the transformer, so repair it promptly.

ElementDetail
Primary sideIn series with the loop, carrying the circuit current
Secondary sideTo one sign only, through a short cable
CouplingMagnetic, with no direct electrical path between the windings
Current ratioCommonly 1:1, for example 6.6 A : 6.6 A
RatingSet size of rated power, covering the sign load
ConnectionSealed connectors, so it can be tested or replaced without re-jointing the loop
Series isolation transformers are specified in IEC 61823 and FAA AC 150/5345-47, and covered in ICAO Doc 9157 Part 5. Available ratings, losses, current ratios and connector types vary by manufacturer and standard, so follow the design drawings, the manufacturer's instructions and the edition in force.
Entry 30 · Sign circuit Entry 32 · Sign connector

Frequently Asked Questions

Q1What is a sign transformer?

A series isolation transformer that connects one sign to the airfield series circuit. Its primary winding is a link in the loop and its secondary feeds only that sign.

Q2Why is the sign isolated from the loop?

The transformer passes energy to the sign magnetically, with no direct electrical path from the primary to the secondary. The sign is kept apart from the series circuit, and the primary loop stays closed if the sign or its secondary cable is disconnected.

Q3How is a sign transformer chosen?

By rated power. Transformers come in set sizes, and the sign's load, meaning its LED module and driver, should sit within the rating chosen. Larger or double-faced signs draw more. The CCR must also carry the sum of every transformer's load on the circuit.

Q4Is it safe to unplug a sign transformer?

Not without isolating the circuit first. The primary connectors are in the series loop, so unplugging one opens the loop and stops every light on it, and the secondary should be treated as live. Isolate and make the circuit safe under site procedures before any work.

Precision AGL Academy

See It. Understand It. Then Learn How to Engineer It.

Recognising an AGL system visually is the first step. The next step is knowing how to design, install, test, commission and maintain them correctly.

Build Practical AGL Engineering Skills

Go deeper with structured training from Precision AGL Academy, covering:

AGL Fundamentals Design & Electrical Engineering Approach Lighting Photometry Installation & Commissioning Maintenance & Troubleshooting

Learn how each light, sign and circuit works as part of a complete airport lighting system, not just as an isolated diagram.

See. Understand. Apply. Engineer.