How is an isolation transformer sized?

Choosing the rating of the small transformer at every light: big enough for the fixture, close enough to its load to run efficiently, and matched to the series circuit.

TRANSFORMER SIZING RATING AT OR ABOVE THE LOAD, AND NOT FAR ABOVE IT ONE FIXTURE · 45 W LAMP · THREE TRANSFORMER OPTIONS loading = fixture load ÷ transformer rating 30/45 W transformer 100% LOADED AT ITS UPPER RATING 65 W transformer 69% LOADED SOME MARGIN 100 W transformer 45% LOADED LIGHTLY LOADED TOO SMALL OVERHEATS · TOO LARGE WASTES POWER WHAT THE TRANSFORMER MUST MATCH 1 FIXTURE POWER lamp or LED draw on the secondary 2 LOADING close to rating, never above it 3 PRIMARY series current and 5 kV class insulation 4 SECONDARY voltage and current suit the lamp or driver 5 FUTURE LAMP CHANGE halogen to LED, or a different wattage 6 EXTRA LOADS signs or anything else on the secondary THE METHOD 1 FIND THE FIXTURE LOAD 2 CHOOSE A RATING 3 MATCH THE PRIMARY 4 MATCH THE SECONDARY 5 CHECK THE LOADING 6 FEED LOAD CALC SCHEMATIC · ILLUSTRATIVE RATINGS · USE THE TRANSFORMER NAMEPLATE AND THE FIXTURE DATA
at its rating
some margin
lightly loaded
what it must match
The Fact Engineering concept

Every light on a series circuit sits behind its own isolation transformer, which couples the fixture to the loop. Transformer sizing picks the rating of that transformer, and because there is one at every light, a small habit repeated hundreds of times shapes the whole circuit load.

1Cover the fixture load

The rating must be at or above the power the fixture draws on the secondary, plus anything else connected there. The figure to use is the fixture’s real draw, not just its lamp label, and for LED fixtures it is far smaller than for the halogen lamp they replace. Standard ratings run in steps (FAA AC 150/5345-47 lists 10/15, 20/25, 30/45, 65, 100, 150, 200, 300 and 500 W), so take the nearest size at or above the real draw rather than an exact match.

SizingWhat happens in the transformerEffect on the circuit
Too smallOverloaded: runs hot, output sags, lamp dims, insulation and life sufferLight output falls and the transformer may fail early
Well matchedNear its rating: best efficiency and power factor for the power deliveredLowest loss, so the lightest load on the constant current regulator (CCR)
Much too largeLightly loaded: low efficiency, magnetising current large for the power deliveredExtra loss on every unit adds to the circuit load

2Stay close to the load

Bigger is not safer. A transformer carrying far less than its rating still draws its magnetising current, so its efficiency and power factor fall. That cost is paid at every light, and it comes back as extra load on the regulator. An overloaded transformer is worse: it overheats and the lamp is dimmer than it should be.

3Match primary and secondary

The primary is wired into the series loop, so it must suit the circuit current, commonly 6.6 A, and the high insulation class of the loop. The secondary voltage and current must suit the lamp or LED driver. All of this is fixed by the nameplate, so sizing is also about reading it correctly. Allow for a likely future lamp change, such as halogen to LED, and note the transformer’s result for the load calculation.

  1. Find the fixture load. Use the fixture data for the lamp or LED module and any extra secondary load.
  2. Choose a rating. Take the nearest standard rating at or above that load.
  3. Match the primary. Series circuit current and insulation class.
  4. Match the secondary. Voltage and current for the lamp or LED driver.
  5. Check the loading. Close to rating, not heavily oversized, not overloaded.
  6. Record the result. Pass the transformer input power into the load calculation.
TermMeaning
RatingPower the transformer is built to deliver, in W or VA
LoadingFixture load as a share of the transformer rating
PrimaryWinding connected to the series loop
SecondaryWinding that feeds the fixture
Magnetising currentCurrent that magnetises the core, drawn even at light load
EfficiencyOutput power as a share of input power, best near rating
Schematic: the 45 W fixture and the 30/45, 65 and 100 W ratings are illustrative (30/45 W is a standard dual-rated size, so it carries a 45 W fixture at its upper rating, while the smaller 10/15 and 20/25 W sizes would be overloaded by it), and the sizing table describes tendencies, not measured values. Standard ratings, efficiency and tolerances come from the transformer specification and datasheet, and always from the nameplate for the unit installed. Series isolation transformers are covered in FAA AC 150/5345-47, IEC 61823 and ICAO Doc 9157, Part 5, so confirm against the editions in force.
Entry 22 · Cable sizing Entry 24 · Circuit loading

Frequently Asked Questions

Q1What is transformer sizing in airfield lighting?

Choosing the power rating of the isolation transformer that feeds each fixture from the series circuit, so it comfortably supplies the fixture load without being so large that it runs inefficiently.

Q2What does the transformer rating have to cover?

At least the power the fixture draws on its secondary, plus any other load on that secondary. The rating is in watts or volt-amperes and sits on the transformer nameplate.

Q3Why not fit a much bigger transformer to be safe?

A lightly loaded transformer is less efficient and draws more magnetising current for the power it delivers. Across a whole circuit those extra losses add to the load the regulator must carry.

Q4What happens if the transformer is too small?

It runs hot, its output is pulled down so the lamp is dimmer than it should be, and its insulation and life suffer. Overloading is the more serious error of the two.

Q5Do LED fixtures need a different transformer?

LED fixtures draw much less than halogen lamps, so the load is small. Use the transformer the fixture manufacturer specifies, and check how it behaves when lightly loaded, rather than assuming the old rating still fits.

Q6What else must match besides power?

The primary must suit the series circuit current, usually 6.6 A, and the high insulation class of the loop, and the secondary voltage and current must suit the lamp or LED driver. These are set on the nameplate.

Precision AGL Academy

See It. Understand It. Then Learn How to Engineer It.

Recognising an AGL system visually is the first step. The next step is knowing how to design, install, test, commission and maintain them correctly.

Build Practical AGL Engineering Skills

Go deeper with structured training from Precision AGL Academy, covering:

AGL Fundamentals Design & Electrical Engineering Approach Lighting Photometry Installation & Commissioning Maintenance & Troubleshooting

Learn how each light, sign and circuit works as part of a complete airport lighting system, not just as an isolated diagram.

See. Understand. Apply. Engineer.