Division 17 of 22 · SOP-341 → SOP-367 Series

AGL Electrical Testing, CCR & Photometric Verification SOPs

Controlled procedures for AGL electrical testing, cable and transformer testing, CCR input/output/current/voltage testing, functional testing of runway, taxiway, approach, PAPI and signage circuits, and photometric testing — covering intensity, beam alignment, chromaticity, instrumentation, calibration verification, test reporting and fully integrated AGL system testing.

27 / 27
Topics Published
SOP-341 → SOP-367
SOP ID Range
Rev 0
Initial Issue

Technical Control — Test methods, acceptance criteria, test voltages, measurement locations, instrument requirements and photometric limits shall be taken from the approved project specifications, applicable ICAO/FAA/DGCA requirements, relevant IS/IEC standards, equipment manufacturer's instructions and approved airport maintenance procedures. Do not use a generic numerical acceptance value where the applicable standard or approved design specifies a different criterion.

Division 17 · Testing & Photometry SOPs

27 of 27 topics published
SOP-341 Insulation Resistance Testing
Purpose

To verify the insulation condition of AGL electrical circuits, cables or equipment using an approved insulation-resistance test method.

Pre-Test Requirements

Verify:

  • Approved test procedure.
  • Circuit identification.
  • Electrical isolation.
  • LOTO.
  • Equipment disconnected/protected where required.
  • Suitable calibrated insulation tester.
  • Correct test voltage.
  • Test points identified.
  • Sensitive electronic equipment isolated/protected.
Procedure
  1. Obtain electrical work authorization.
  2. Identify circuit/equipment.
  3. Isolate circuit.
  4. Apply LOTO.
  5. Prove dead.
  6. Disconnect components that could be damaged by the test.
  7. Connect insulation tester.
  8. Apply approved test voltage.
  9. Record stabilized measurement according to the approved method.
  10. Stop test.
  11. Discharge stored electrical energy.
  12. Restore connections.
  13. Compare result with approved criterion.
  14. Record test result.

Important — Never apply an insulation-resistance test to connected electronic equipment unless the manufacturer specifically permits it.

SOP-342 Continuity Testing
Purpose

To verify electrical continuity of conductors and circuit paths.

Procedure
  1. Identify circuit.
  2. Isolate equipment.
  3. Verify absence of hazardous voltage.
  4. Select appropriate continuity instrument.
  5. Connect test leads.
  6. Measure continuity.
  7. Compare with approved requirement.
  8. Investigate abnormal readings.
  9. Restore connections.
  10. Record results.
Typical Applications
  • Cable conductors.
  • Secondary leads.
  • Bonding conductors.
  • Control wiring.
  • Connector circuits.
SOP-343 Earth Resistance Testing
Purpose

To determine the resistance characteristics of the applicable earthing system.

Procedure
  1. Confirm no thunderstorm/lightning activity in the vicinity; suspend earth testing when lightning is forecast or observed.
  2. Review approved earthing design.
  3. Identify earth electrode/system.
  4. Select approved test method.
  5. Verify instrument calibration.
  6. Isolate parallel paths where required by the test method.
  7. Connect test instrument.
  8. Perform measurement.
  9. Repeat/verify reading where required.
  10. Record test conditions.
  11. Compare against approved acceptance criterion.
  12. Restore earth connections.
Record

Record:

  • Earth point.
  • Test method.
  • Instrument.
  • Test date.
  • Environmental conditions where relevant.
  • Measured result.
  • Acceptance criterion.
  • Pass/Fail.
SOP-344 Earth Continuity Testing
Purpose

To verify continuity of protective-earth and bonding conductors.

Procedure
  1. Identify equipment.
  2. Identify earth points.
  3. Isolate equipment where necessary.
  4. Connect continuity tester.
  5. Measure continuity.
  6. Check connections.
  7. Investigate abnormal resistance.
  8. Repair where authorized.
  9. Retest.
  10. Record.
SOP-345 Cable Testing
Purpose

To verify the electrical integrity of AGL primary and secondary cables before commissioning, after repair or as part of periodic maintenance.

Test Scope

Depending on cable type and approved test plan:

  • Continuity.
  • Insulation resistance.
  • Conductor identification.
  • Phase/circuit identification.
  • Sheath condition where applicable.
  • Connection integrity.
  • Other approved tests.
Procedure
  1. Identify cable.
  2. Confirm cable schedule.
  3. Isolate cable.
  4. Apply LOTO where required.
  5. Disconnect sensitive equipment.
  6. Perform approved tests.
  7. Record results.
  8. Compare against specification.
  9. Restore connections.
  10. Update test records.
SOP-346 Cable Insulation Testing
Purpose

To evaluate the insulation condition of AGL cables.

Procedure
  1. Identify cable.
  2. Isolate both ends as required.
  3. Verify absence of voltage.
  4. Disconnect equipment that may be damaged.
  5. Select approved test voltage.
  6. Connect tester.
  7. Perform test.
  8. Record result.
  9. Discharge cable after test.
  10. Reconnect equipment.
  11. Repeat where required.
  12. Document result.

Critical Point — Long AGL cables can retain electrical charge after testing. Always follow the approved discharge procedure before touching or reconnecting conductors.

SOP-347 Transformer Testing
Purpose

To verify the electrical and physical condition of AGL isolation transformers.

Test Areas

As applicable:

  • Visual condition.
  • Continuity.
  • Insulation resistance.
  • Ratio.
  • Output.
  • Polarity.
  • Nameplate verification.
  • Connection condition.
Procedure
  1. Identify transformer.
  2. Verify rating/nameplate.
  3. Isolate transformer.
  4. Inspect physically.
  5. Perform approved electrical tests.
  6. Record results.
  7. Compare with manufacturer/project criteria.
  8. Reconnect.
  9. Conduct functional verification.
SOP-348 Transformer Ratio Testing
Purpose

To verify the transformer turns ratio against the approved transformer specification.

Procedure
  1. Identify transformer.
  2. Verify nameplate.
  3. Isolate transformer.
  4. Use appropriate ratio-test equipment.
  5. Connect according to instrument instructions.
  6. Perform measurement.
  7. Record ratio.
  8. Compare with manufacturer's specified ratio/tolerance.
  9. Disconnect test equipment.
  10. Restore normal configuration.
SOP-349 Transformer Output Testing
Purpose

To verify transformer output under the approved test conditions.

Procedure
  1. Verify transformer rating.
  2. Confirm the secondary load/open-circuit condition permitted by the manufacturer — an open secondary on a current-fed series transformer can generate hazardous voltage.
  3. Confirm test configuration.
  4. Energize only under controlled conditions.
  5. Measure approved output parameter(s).
  6. Record input/output conditions.
  7. Compare against specification.
  8. De-energize if required.
  9. Discharge/isolate as applicable.
  10. Record result.
SOP-350 CCR Input Testing
Purpose

To verify the electrical supply provided to the CCR.

Verify
  • Input voltage.
  • Frequency.
  • Phase arrangement.
  • Protective devices.
  • Input connections.
  • Earthing.
Procedure
  1. Obtain authorization.
  2. Follow electrical safety procedure.
  3. Verify instrument rating.
  4. Measure input parameters.
  5. Compare against CCR requirements.
  6. Record results.
  7. Investigate abnormalities.
SOP-351 CCR Output Testing
Purpose

To verify CCR output performance.

Procedure
  1. Confirm CCR identification.
  2. Confirm output circuit configuration.
  3. Verify test equipment.
  4. Operate CCR at approved condition.
  5. Measure output parameters.
  6. Test required operating steps.
  7. Verify protection.
  8. Record results.
  9. Compare against approved limits.
SOP-352 CCR Current Testing
Purpose

To verify actual series-circuit current generated by the CCR.

Procedure
  1. Identify CCR/circuit.
  2. Verify safe test configuration.
  3. Never break the series loop or open a current-transformer secondary while energized to insert an instrument.
  4. Use calibrated suitable instrument.
  5. Operate CCR at approved intensity steps.
  6. Measure current at each required step.
  7. Record actual values.
  8. Compare against approved CCR settings/tolerances.
  9. Investigate abnormal deviations.

Important — For a series AGL circuit, current regulation is a fundamental operating parameter. A current reading must be interpreted together with the CCR setting and circuit condition.

SOP-353 CCR Voltage Testing
Purpose

To verify CCR output voltage under defined operating conditions.

Procedure
  1. Confirm test authorization.
  2. Verify instrument category/rating.
  3. Verify test configuration.
  4. Operate CCR under approved condition.
  5. Measure output voltage.
  6. Record current simultaneously where required.
  7. Compare with expected system condition.
  8. Investigate abnormal values.
SOP-354 Functional Testing
Purpose

To verify that AGL equipment performs its intended function after installation, maintenance or modification.

Functional Test

Depending on system:

  • Start/stop.
  • Brightness.
  • Switching.
  • Control response.
  • Alarm.
  • Interlock.
  • Remote control.
  • Feedback.
  • Communication.
  • Operational lighting.
Procedure
COMMANDEQUIPMENT RESPONSEFIELD RESPONSEFEEDBACKALARM/EVENT RECORD

shall be verified where applicable.

SOP-355 Runway Light Testing
Purpose

To verify runway light operational, electrical, optical and mechanical condition.

Test
  • ON/OFF.
  • Brightness.
  • Optical output.
  • Alignment.
  • Colour.
  • Mechanical condition.
  • Electrical connection.
  • Control response.
Procedure
  1. Identify fixture.
  2. Verify circuit.
  3. Energize under approved conditions.
  4. Verify operation.
  5. Inspect optical output.
  6. Check alignment.
  7. Check physical condition.
  8. Record defects.
SOP-356 Taxiway Light Testing
Purpose

To verify taxiway lighting operational and visual performance.

Verify
  • Taxiway edge lights.
  • Centreline lights.
  • Curve lighting.
  • Junction lighting.
  • RET lighting.
  • Lead-on/lead-off systems.
  • Stop bars where applicable.
Procedure
  1. Identify circuit.
  2. Verify operational condition.
  3. Check fixture response.
  4. Check alignment.
  5. Verify brightness/control.
  6. Record defective fixtures.
SOP-357 Approach Light Testing
Purpose

To verify the operational and optical condition of the approach lighting system.

Test
  • Fixture operation.
  • Light output.
  • Alignment.
  • Height.
  • Orientation.
  • Circuit response.
  • Control response.
Procedure
  1. Establish safe test conditions.
  2. Energize system.
  3. Inspect fixture sequence.
  4. Verify operation.
  5. Check alignment.
  6. Record defective/misaligned fixtures.
SOP-358 PAPI Testing
Purpose

To verify PAPI operational and optical performance.

Test Areas
  • Electrical operation.
  • Light output.
  • Colour transition.
  • Optical condition.
  • Alignment.
  • Elevation setting.
  • Heater operation where applicable.
  • Control/power supply.

Important — Routine functional testing does not replace the formal PAPI alignment and photometric verification procedure.

SOP-359 Signage Testing
Purpose

To verify airfield sign electrical, illumination and functional performance.

Test
  • ON/OFF.
  • Illumination.
  • Brightness.
  • Message visibility.
  • Electrical connection.
  • Control response.
  • Emergency/backup function where applicable.
SOP-360 Photometric Testing
Purpose

To measure and assess the photometric performance of AGL light sources against the applicable technical criteria.

Applications
  • Runway lights.
  • Taxiway lights.
  • Approach lights.
  • PAPI.
  • Signs where applicable.
  • Other visual aids.
Pre-Test

Verify:

  • Approved test method.
  • Applicable standard.
  • Test geometry.
  • Photometric instrument.
  • Calibration status.
  • Ambient conditions.
  • Fixture condition.
  • CCR setting.
  • Test circuit.
  • Test location.
Procedure
  1. Establish test area.
  2. Confirm fixture identification.
  3. Set approved CCR intensity.
  4. Position photometric instrument.
  5. Verify measurement geometry.
  6. Perform measurements.
  7. Record values.
  8. Repeat where required.
  9. Compare with applicable criteria.
  10. Identify failures/deviations.
  11. Prepare test report.
SOP-361 Light Intensity Measurement
Purpose

To measure the luminous intensity of an AGL light fixture in specified directions.

Procedure
  1. Verify calibrated photometer.
  2. Establish measurement geometry.
  3. Verify fixture orientation.
  4. Set required operating condition.
  5. Measure intensity at specified points/angles.
  6. Record values.
  7. Repeat measurements where required.
  8. Compare with applicable photometric criteria.

Important — A single intensity reading does not establish compliance with a complete photometric distribution requirement.

SOP-362 Beam Alignment Verification
Purpose

To verify that an AGL fixture's optical beam is correctly oriented.

Procedure
  1. Identify fixture.
  2. Establish reference line.
  3. Establish required measurement geometry.
  4. Set fixture to approved operating condition.
  5. Measure beam direction.
  6. Compare against approved alignment requirement.
  7. Adjust fixture where authorized.
  8. Retest.
  9. Record final alignment.
SOP-363 Chromaticity Verification
Purpose

To verify that emitted light falls within the applicable chromaticity requirements.

Procedure
  1. Verify calibrated colour/chromaticity measurement equipment.
  2. Confirm the chromaticity boundaries for the light function (ICAO Annex 14 Vol. I, Appendix 1, or the applicable national standard).
  3. Establish test geometry.
  4. Operate fixture at approved condition.
  5. Measure chromaticity.
  6. Record coordinates/values.
  7. Compare with applicable chromaticity boundaries.
  8. Investigate non-compliant results.
  9. Retest after corrective action.
Applications

May include:

  • White.
  • Red.
  • Green.
  • Yellow/amber.
  • Other approved aviation lighting colours.
Note

The exact colour requirements shall be taken from the applicable standard for the particular light function.

SOP-364 Photometry Instrument Setup
Purpose

To ensure photometric instruments are correctly prepared and positioned before testing.

Setup

Verify:

  • Instrument identity.
  • Calibration status.
  • Battery/power.
  • Measurement range.
  • Detector configuration.
  • Zero/reference condition.
  • Data storage.
  • Tripod/fixture stability.
  • Measurement distance.
  • Alignment.
  • Ambient conditions.
Procedure
  1. Inspect instrument.
  2. Verify calibration validity.
  3. Configure measurement parameters.
  4. Establish measurement geometry.
  5. Level/align instrument.
  6. Verify reference/zero.
  7. Confirm data capture.
  8. Conduct test.
SOP-365 Photometry Instrument Calibration Verification
Purpose

To verify that the photometric instrument has valid calibration before use.

Verify
  • Instrument ID.
  • Calibration certificate.
  • Calibration date.
  • Due date.
  • Applicable measurement range.
  • Detector condition.
  • Reference check where required.
Procedure
  1. Inspect calibration certificate.
  2. Confirm calibration status.
  3. Check instrument condition.
  4. Perform pre-use verification/reference check if required.
  5. Record verification.
  6. Remove instrument from service if calibration is expired or validity is questionable.

Critical Rule — Calibration validity and pre-use verification are different controls.

SOP-366 Photometry Test Report Preparation
Purpose

To ensure photometric test results are documented in a technically traceable format.

A. Project Information
  • Airport.
  • Location.
  • Runway/taxiway/approach identifier.
  • Test date.
  • Test purpose.
B. Equipment
  • Fixture type.
  • Manufacturer.
  • Model.
  • Serial number where available.
  • Fixture identification.
C. Test Equipment
  • Instrument.
  • Instrument serial number.
  • Calibration status.
D. Test Conditions
  • CCR setting.
  • Test geometry.
  • Measurement distance.
  • Ambient conditions where relevant.
  • Test method.
  • Applicable standard/specification.
E. Results
  • Measurement points.
  • Measured intensity.
  • Beam alignment.
  • Chromaticity where applicable.
  • Acceptance criteria.
  • Pass/Fail.
  • Observations.
F. Traceability
  • Technician.
  • Reviewer.
  • Test reference number.
  • Instrument certificate reference.
  • Photographs where required.
  • Corrective action/retest reference.
Report Flow
RAW DATAVALIDATIONENGINEERING REVIEWACCEPTANCE ASSESSMENTFINAL REPORTAPPROVALCONTROLLED RECORD
SOP-367 Integrated AGL System Testing
Purpose

To verify the complete AGL chain from electrical supply and CCR through series circuits, transformers, fixtures, control systems and operational/photometric performance.

Electrical Scope
  • Incoming supply.
  • CCR.
  • Series circuit.
  • Cable.
  • Transformer.
  • Secondary circuit.
  • Earthing/bonding.
Control Scope
  • ALCMS.
  • PLC.
  • HMI.
  • CCR remote control.
  • Brightness control.
  • Communication.
Field Equipment Scope
  • Runway lights.
  • Taxiway lights.
  • Approach lights.
  • PAPI.
  • Signs.
  • Stop bars.
  • RGL.
Performance Scope
  • Functional operation.
  • Intensity.
  • Alignment.
  • Chromaticity where applicable.
  • Alarm response.
  • Feedback.
Note

The full seven-stage integrated test sequence (Documentation → Electrical → CCR → Series Circuit → Control → Photometry → Final Acceptance) is set out in the Division 17 Master Workflow below.

No SOPs match your search. Try a different keyword.

Division-Wide Requirements

Master testing workflow, quality hold points, master testing checklist, common testing failures and required records that apply across all 27 Division 17 procedures.

A. Integrated AGL Test Sequence — Master Workflow

The following stage sequence should be applied whenever a full or integrated AGL test is required:

Stage 1 — Documentation

APPROVED DRAWINGSEQUIPMENT SCHEDULECABLE SCHEDULECIRCUIT SCHEDULEAPPROVED TEST PLAN

Stage 2 — Electrical

CABLE CONTINUITYCABLE INSULATIONTRANSFORMER TESTINGEARTHING/BONDINGCCR INPUT

Stage 3 — CCR

CCR STARTOUTPUT CURRENTOUTPUT VOLTAGEPROTECTIONBRIGHTNESS STEPS

Stage 4 — Series Circuit

CIRCUIT ENERGIZATIONCIRCUIT CURRENTTRANSFORMER RESPONSEFIXTURE RESPONSE

Stage 5 — Control

ALCMS COMMANDPLC RESPONSECCR RESPONSEFIELD LIGHTING RESPONSEALCMS FEEDBACK

Stage 6 — Photometry

INSTRUMENT CALIBRATION VERIFICATIONINSTRUMENT SETUPGEOMETRY VERIFICATIONINTENSITY MEASUREMENTALIGNMENT VERIFICATIONCHROMATICITY VERIFICATION

Stage 7 — Final Acceptance

TEST RESULTS REVIEWDEFECT LISTCORRECTIVE ACTIONRETESTFINAL FUNCTIONAL TESTTEST REPORTENGINEERING ACCEPTANCERETURN TO SERVICE

B. Testing Quality Hold Points (HP-01 → HP-12)

Work shall not proceed past a hold point until the associated inspection or verification has been completed and released.

  • HP-01 — Test Documentation: Approved drawings, specifications and test procedures available.
  • HP-02 — Instrument Calibration: All measuring instruments have valid calibration status.
  • HP-03 — Electrical Safety: Isolation/LOTO/proving-dead requirements completed before applicable tests.
  • HP-04 — Cable Testing: Cable test results accepted before energization.
  • HP-05 — Transformer Testing: Transformer test results accepted.
  • HP-06 — CCR Testing: Input/output/current/voltage/protection verified.
  • HP-07 — Functional Testing: Equipment performs its intended function.
  • HP-08 — Photometry Setup: Measurement geometry and instrument setup verified.
  • HP-09 — Photometric Results: Results reviewed against the applicable criteria.
  • HP-10 — Corrective Action: Failed items repaired and retested.
  • HP-11 — Integrated Testing: Complete AGL chain successfully verified.
  • HP-12 — Final Acceptance: Controlled test report approved.

C. Master Testing Checklist

The following items should be confirmed, as applicable, before AGL testing is closed out:

  • Approved test procedure available
  • Approved drawings available
  • Applicable specification identified
  • Acceptance criteria identified
  • Test equipment identified
  • Calibration verified
  • Electrical safety controls completed
  • LOTO completed where required
  • Proving-dead completed where required
  • Cable continuity tested
  • Cable insulation tested
  • Earth resistance tested
  • Earth continuity tested
  • Transformer tested
  • Transformer ratio verified
  • Transformer output verified
  • CCR input verified
  • CCR output verified
  • CCR current verified
  • CCR voltage verified
  • Functional testing completed
  • Runway lights tested
  • Taxiway lights tested
  • Approach lights tested
  • PAPI tested
  • Signs tested
  • Photometric instrument setup verified
  • Photometric calibration verified
  • Intensity measured
  • Beam alignment verified
  • Chromaticity verified where applicable
  • Raw data retained
  • Failed items identified
  • Corrective actions completed
  • Retesting completed
  • Integrated AGL testing completed
  • Test report prepared
  • Technical review completed
  • Final acceptance completed

D. Common Testing Failures to Monitor

The following conditions should be specifically monitored during Division 17 testing:

  1. Testing Without Correct Isolation — Can expose personnel or equipment to hazardous energy.
  2. Insulation Testing With Electronics Connected — Can damage controllers, drivers, communication interfaces and electronic modules.
  3. Incorrect Earth Resistance Method — Parallel earth paths can produce misleading measurements.
  4. Wrong CCR Operating Step — Photometric measurements taken at the wrong intensity setting can produce invalid conclusions.
  5. Incorrect Photometry Geometry — Even a calibrated instrument can produce unreliable results if distance, height, orientation or reference geometry is wrong.
  6. Expired Calibration — Measurements may not be technically defensible if the instrument's calibration status is invalid.
  7. One-Point Photometry — One intensity measurement cannot necessarily establish full compliance with an applicable photometric distribution requirement.
  8. Ignoring Chromaticity — A light may appear visually acceptable while its measured chromaticity falls outside the applicable requirement.
  9. Testing Without Traceability — A result without Equipment ID + Location + Instrument + Date + Test Method + Acceptance Criterion has limited engineering value.
  10. No Retest After Repair — A repaired component should not automatically be considered compliant without the required verification.

Division 17 — Required Records

The AGL testing organization should maintain, as applicable, a Master Test Record covering:

  • Insulation Resistance
  • Continuity
  • Earth Resistance
  • Earth Continuity
  • Cable
  • Transformer
  • Transformer Ratio
  • Transformer Output
  • CCR Input
  • CCR Output
  • CCR Current
  • CCR Voltage
  • Functional
  • Runway Lighting
  • Taxiway Lighting
  • Approach Lighting
  • PAPI
  • Signage
  • Photometry
  • Intensity
  • Beam Alignment
  • Chromaticity
  • Integrated AGL

Each record entry should carry, at minimum, the following traceability fields:

  • Test Category / Test ID
  • Equipment/Location
  • Instrument
  • Result
  • Acceptance Criterion
  • Status (Pass/Fail)
  • Technician
  • Reviewer
  • Test Reference Number
  • Instrument Certificate Reference
  • Photographs where required
  • Corrective Action/Retest Reference

Division 17 — AGL Testing Golden Rule

“A test result is meaningful only when the equipment, test method, instrument, calibration status, test condition, measurement geometry and acceptance criterion are all controlled and traceable. AGL testing shall progress from electrical integrity → equipment performance → control response → field operation → photometric performance → integrated system verification.”

Division 17 — SOP Approval Principle

Test methods, acceptance criteria, test voltages, measurement locations, instrument requirements and photometric limits shall be taken from the approved project specifications, applicable ICAO/FAA/DGCA requirements, relevant IS/IEC standards, equipment manufacturer's instructions and approved airport maintenance procedures.

Generic numerical acceptance values shall not be substituted where the applicable standard or approved design specifies a different criterion — approved project specifications and applicable standards shall always take precedence.

Reference Basis

Technical references behind the procedures in this division:

  • ICAO Annex 14, Vol. I — Aerodrome Design and Operations, Appendix 1 (colours) and Appendix 2 (light characteristics) — colour and intensity criteria against which measurements are assessed.
  • ICAO Doc 9157, Aerodrome Design Manual, Part 4 — photometric measurement guidance.
  • FAA AC 150/5345-46, AC 150/5345-28 and AC 150/5345-44 — equipment photometric requirements.
  • FAA AC 150/5340-26 and IEC 61821 — maintenance testing of series circuits.
  • CIE 121 and CIE 15 — photometry and goniophotometry; colorimetry.
  • IEC 61557 series and IEC 60364-6 — insulation, continuity and earth-resistance test equipment; verification of installations.
  • ISO/IEC 17025 — competence and traceability of calibration and test laboratories.
  • FAA AC 150/5345-53 — certified equipment.

References are given at document or chapter level for technical orientation. Confirm the current edition, amendments and national adoption (for example DGCA CAR Section 4, FAA Advisory Circulars or EASA material) for each project. Approved project specifications, manufacturer instructions and the airport's own procedures take precedence, as stated in the precedence note above.

Frequently Asked Questions

Quick answers about Testing & Photometry SOPs in the AGL SOP Library.

Q1What is Division 17 — Testing & Photometry SOPs?

Division 17 is a set of 27 procedures (SOP-341 to SOP-367, Rev 0) for AGL electrical testing, cable and transformer testing, CCR input, output, current and voltage testing, and functional testing of runway, taxiway, approach, PAPI and signage circuits. It also covers photometric testing (intensity, beam alignment, chromaticity), instrumentation, calibration verification, test reporting and integrated AGL system testing.

Q2Where do test methods and acceptance criteria come from?

The approved project specifications, applicable ICAO, FAA and DGCA requirements, relevant IS/IEC standards, manufacturer's instructions and approved airport maintenance procedures. A generic numerical acceptance value must not be used where the applicable standard or approved design specifies a different criterion.

Q3What must be in place before an insulation resistance test?

An approved test procedure, circuit identification, electrical isolation and LOTO, equipment disconnected or protected where required, a calibrated insulation tester, the correct test voltage, identified test points and protection for sensitive electronic equipment (SOP-341). The circuit is proved dead before testing begins.

Q4What does photometric testing involve?

SOP-360 measures the photometric performance of AGL light sources such as runway, taxiway and approach lights, PAPI and signs where applicable. Before testing, verify the approved method, applicable standard, test geometry, instrument and its calibration status, ambient conditions, fixture condition, CCR setting and test location. Then set the approved CCR intensity, position the instrument and record the measurements.

Q5Is a valid calibration certificate enough before using a photometric instrument?

No. Calibration validity and pre-use verification are different controls (SOP-365). Check the instrument ID, certificate, calibration and due dates, measurement range and detector condition, perform a pre-use reference check if required, and remove the instrument from service if calibration is expired or questionable.

Q6What does integrated AGL system testing cover?

SOP-367 verifies the complete chain from incoming supply and CCR through series circuits, cables, transformers, secondary circuits and earthing to the control scope (ALCMS, PLC, HMI, remote control and communication) and the field equipment. Performance checks include operation, intensity, alignment, chromaticity where applicable, alarm response and feedback.

Precision AGL Academy

Turn SOP Knowledge Into AGL Engineering Competence.

Knowing the test procedure is essential. Understanding how photometric and electrical test results relate to AGL compliance takes deeper technical knowledge.

Build Practical AGL Expertise

Learn through structured training covering: