What is open-circuit protection (OCP)?

A series circuit is one loop, and a constant current regulator will push its set current through whatever it is given. If the loop breaks, open-circuit protection stops the regulator before its voltage climbs, and tells the control system.

SERIES CIRCUIT · A BREAK IN THE LOOP AND THE CCR’S OPEN-CIRCUIT PROTECTION CCR OUTPUT CURRENT SENSE OCP LOGIC OUTPUT CONTACTOR OUTPUT SHUT DOWN ON TRIP BREAK · OPEN ENDS HIGH VOLTAGE IF ENERGISED ISOLATION TRANSFORMERS · LAMPS OUT EVERY LAMP ON THE CIRCUIT GOES OUT ALARM · CONTROL SYSTEM / TOWER OUTPUT VOLTAGE AFTER THE BREAK WITHOUT OCP · CLIMBS TOWARD THE CCR MAXIMUM WITH OCP · TRIPS, OUTPUT OFF TIME → 1 · BREAKNo current path, all lamps out 2 · SENSECCR sees no current and rising volts 3 · TRIPOutput off, fault latched, alarm raised OCP LIMITS THE VOLTAGE AND THE DAMAGE · THE BREAK STILL HAS TO BE FOUND AND REPAIRED
primary series loop
break / alarm
CCR
protected response
The Fact IEC 61822 · FAA AC 150/5345-10

Open-circuit protection is the part of a CCR that shuts the output down when the series loop opens. It turns a dangerous no-load condition into a controlled trip and an alarm.

1Why an open circuit is dangerous

A CCR holds a set current. When the loop breaks the current falls to zero, so the CCR raises its output voltage to try to restore it. That voltage climbs toward the CCR's maximum, appears across the break, and stresses insulation, connectors and transformers. It is also a hazard to anyone near the open ends.

2How it is detected

The CCR senses its own output. Little or no current while the output is on, together with a rising voltage, tells the control logic that the loop is open. A short delay avoids tripping on a momentary dip. Thresholds and delays are set by the manufacturer.

3What it does

The CCR opens its output, the lamps go out, and the fault is latched and reported to the control system, often as an open-circuit alarm. The CCR stays tripped until it is reset. A single failed lamp does not do this, because the isolation transformer keeps the primary loop closed and its film cutout shorts the secondary.

4After the trip

The circuit is isolated, locked out and proved dead before work starts, because the cable ends at a break can still be hazardous. The team then splits the loop and tests each section for continuity to find the break, repairs it, and only then resets. Repeated resets apply high voltage to the same fault and can hide the cause.

ConditionNormalOpen circuit, no OCPOpen circuit, OCP trips
Loop currentSet step valueFalls to zeroFalls to zero, output shut off
Output voltageWhat the load needsClimbs toward the CCR maximumRises briefly, then removed
LampsLitAll outAll out
AlarmNoneOnly if monitored elsewhereOpen-circuit alarm raised
Risk at the breakNoneHigh voltage, arcingLimited, but isolate and prove dead before work
Teaching schematic. Trip thresholds, delays and reset behaviour differ between CCR models, so real settings come from the manufacturer's manual and the project specification. The curves are illustrative. Isolate and lock out before touching a series circuit or opening the cabinet.
Entry 18 · Film cutout operation Entry 20 · Lamp-out behaviour in a series circuit

Frequently Asked Questions

Q1What does open-circuit protection do?

It shuts the constant current regulator's output down when the series loop is broken. Without it the regulator would keep trying to force the set current through the break, and its output voltage would climb toward its maximum.

Q2Why not just leave the regulator running?

A series circuit is one loop, so a break stops all current. A constant current regulator reacts by raising its voltage to try to restore the current. That puts high voltage across the break and stresses the cable, connectors and transformers, and it is a hazard to anyone near the open ends.

Q3Does a failed lamp trigger it?

No. A lamp sits on the secondary side of its isolation transformer, and the transformer is designed so the primary loop stays closed, with a film cutout shorting the secondary. A single failed lamp dims nothing else and does not open the loop, so it does not trip the protection.

Q4How does the regulator know the circuit is open?

It senses its output. Little or no output current while the regulator is on, together with a rising output voltage, tells the control logic that the loop is open. A short delay avoids tripping on a momentary dip, and the delay and thresholds are set by the manufacturer.

Q5Why should I not keep resetting the regulator after a trip?

The trip means there is a real break somewhere. Each reset applies high voltage to the same fault, which can damage more equipment and hide the cause. The break should be found and repaired before the regulator is reset.

Q6Is the circuit safe once the protection has tripped?

Not automatically. The cable ends at a break can still be hazardous, so the circuit is isolated, locked out and proved dead under the site's procedure before anyone works on it.

Precision AGL Academy

See It. Understand It. Then Learn How to Engineer It.

Recognising an AGL system visually is the first step. The next step is knowing how to design, install, test, commission and maintain them correctly.