What is the series circuit fault path?

Where the current actually goes once a fault changes the loop — nowhere, through a shortcut, or round the loop with a leak to earth.

SERIES LOOP · WHERE DOES THE CURRENT GO? ISOLATE & LOCK OUT BEFORE TOUCHING CABLE ENDS A OPEN CIRCUIT T1 T2 T3 CCR PATH NONE · LOOP BROKEN LAMPS ALL OUT TESTER OVER-RANGE (OL) B SHORT CIRCUIT T1 T2 T3 CCR PATH SHORTCUT, REST SKIPPED LAMPS BEYOND SHORT OUT TESTER FAR BELOW BASELINE C EARTH FAULT T1 T2 T3 CCR PATH LOOP INTACT + LEAK LAMPS STAY ON INSUL. LOW TO EARTH A SECOND EARTH FAULT ELSEWHERE BEHAVES LIKE B SCHEMATIC · LOOP SHORTENED · NOT TO SCALE
series loop (primary cable)
fault / break
secondary
lamp lit
lamp out
The Fact Series circuit fault

A healthy series circuit has exactly one current path: out from the CCR, through the primary cable and every isolation transformer primary in turn, and back. The fault path is the route current takes once a fault changes that loop.

An open circuit removes the path, so no current flows and every lamp goes out. A short circuit adds a shortcut that bypasses the rest of the loop, so fixtures beyond it go dark. An earth fault leaves the loop intact with a leak to earth, so lights usually stay on, until a second fault gives current a path through the ground. The circuit is isolated and proved dead before it is touched.

  1. Normal path. One closed loop through every transformer primary in series.
  2. Fault appears. A break, a bridge between conductors, or a leak to earth.
  3. Current re-routes. None, via the shortcut, or round the loop with a leak.
  4. Read the symptoms. All dark, partly dark, or all lit.
  5. Isolate and test. CCR off, locked out and tagged, proved dead and earthed at the work point (see Circuit Isolation); then continuity and insulation tests.
  6. Locate & repair. Split the loop, test each section, repair, then re-test.
Normal path One closed loop through all primaries in series
Open circuit No path; all lamps out; tester reads OL
Short circuit Shortcut; section beyond is bypassed and dark
Earth fault Loop intact with a leak; lights usually stay on
Tell them apart Lamp pattern, continuity and insulation tests
Reference ICAO Doc 9157 Pt 5; FAA AC 150/5340-26
Schematic — loop shortened for clarity. Always follow your site’s isolation and permit-to-work procedure and the equipment manufacturer’s instructions; fault-finding methods and acceptable values are set by the applicable standard and the commissioning record.
Entry 13 · Earth fault Entry 15 · Circuit zoning

Frequently Asked Questions

Q1What is a fault path in a series lighting circuit?

The route current actually takes once the normal loop has been changed by a fault. A healthy circuit has one route, out from the CCR through every transformer primary in turn and back. A fault removes it, shortens it or adds a leak to earth.

Q2What is the normal current path?

A single closed loop. The CCR drives a regulated current through the primary cable and every isolation transformer primary in series and back to the CCR. The same current flows through every part of the loop.

Q3Where does current go in an open circuit?

Nowhere. The break leaves no complete path, so current stops in the whole circuit, every lamp goes out and the CCR's open-circuit protection acts.

Q4Where does current go in a short circuit?

Through the shortcut. The fault bridges the loop conductors, so current skips the section beyond it. Fixtures before the short usually stay lit, and fixtures beyond it are bypassed and dark.

Q5Where does current go in an earth fault?

The loop stays intact and the circuit current keeps flowing round it, with a small leak to earth at the fault. Lights usually stay on. A second earth fault elsewhere can give current a path through the ground that bypasses the section between the two faults.

Q6How do you tell the fault paths apart in the field?

From the symptoms and then the tests. All lights out with an over-range continuity reading points to an open circuit. A dark section with very low resistance points to a short circuit. Lights still on with poor insulation resistance to earth points to an earth fault. The circuit is isolated and proved dead before any test.

Precision AGL Academy

See It. Understand It. Then Learn How to Engineer It.

Recognising an AGL system visually is the first step. The next step is knowing how to design, install, test, commission and maintain them correctly.