Is the reading falling, even though it still passes?

One megohm reading says whether a circuit passes today. A series of readings says where it is heading. A slow decline can be caught and repaired long before the value reaches the minimum.

1 · THE TREND: READINGS AGAINST TIME 2 · COMPARABLE READINGS, THEN ACTION INSULATION RESISTANCE, MEGOHMS (LOG SCALE) 1000 100 10 BASELINE YR 1 YR 2 YR 3 YR 4 ALERT LEVEL MINIMUM (SPEC) SOUND: FLAT, SEASONAL WIGGLE SLOW DECLINE: ACT AT THE ALERT LEVEL SUDDEN STEP: A NEW FAULT PLOT EVERY READING OF EVERY CIRCUIT AGAINST ITS BASELINE TREND = SLOPE + STEPS, NOT ONE NUMBER A PASS TODAY CAN STILL BE A CIRCUIT HEADING FOR FAILURE KEEP EVERY READING COMPARABLE SAME TEST VOLTAGE AND SAME TIME TO READING SAME CIRCUIT SECTION AND SAME TEST POINT SAME TESTER, IN CALIBRATION CORRECT TO A REFERENCE TEMPERATURE NOTE THE WEATHER, MOISTURE AND CABLE ENDS CCR LOCKED OUT AND DISCONNECTED ACTION LADDER FLAT OR SEASONAL: KEEP THE ROUTINE INTERVAL FALLING TOWARD ALERT: RETEST SOONER, SPLIT LOOP STEP DROP OR BELOW MINIMUM: LOCATE AND REPAIR COMPARE CORRECTED READINGS TO THE BASELINE R(ref) = R(measured) × 2^((T − Tref) ÷ 10) RULE OF THUMB: RESISTANCE ROUGHLY HALVES PER 10 °C RISE USE THE CORRECTION TABLE FOR THE CABLE TYPE BASELINE · SAME CONDITIONS · CORRECT FOR TEMPERATURE · PLOT · READ THE SLOPE · SET AN ALERT LEVEL · ACT EARLY
sound: flat or seasonal
falling toward the alert level
step drop or below the minimum
The Fact Testing & commissioning

Insulation-resistance trend analysis compares the readings taken on the same circuit at each test over the years, instead of judging each one alone. A single reading only shows whether the circuit is above the minimum today. The trend shows whether the insulation is steady, slowly wearing out or has just been damaged, so work can be planned before the circuit fails or an earth fault grounds the loop.

1Start with a baseline

The first point on the chart is the reading taken at commissioning, when the cable and joints were new and dry. Record it with everything needed to repeat the test: the circuit and section, the test voltage and the time to reading, the tester and its calibration date, the temperature and the weather. Every later reading is judged against this baseline, so a circuit with no baseline can only be compared with the minimum.

2Make each reading comparable

A trend is only as good as the conditions behind it. A change in the method looks like a change in the cable. Keep these the same each time:

Keep the sameWhy it matters
Test voltage and time to readingInsulation resistance rises with time under voltage, so a 10-second and a 1-minute reading are not comparable
Circuit section and test pointA different length of cable has a different resistance
Tester, in calibrationInstrument error would show up as a trend
Reference temperatureResistance falls as the cable warms, so correct readings to one temperature
Weather and cable-end conditionDamp soil, wet joints and dirty terminations lower the reading without changing the cable

3Correct for temperature

Insulation resistance falls as the cable gets warmer, so a summer reading is lower than a winter one on the same sound cable. Correct each reading to a reference temperature, often 20 °C, before it goes on the chart. A common rule of thumb for many insulation materials is that resistance roughly halves for every 10 °C of warming:

Rref = Rmeasured × 2(T − Tref) ÷ 10T is the cable temperature at the test and Tref the reference temperature. Illustration: 400 MΩ measured at 30 °C corrects to about 800 MΩ at 20 °C. Use the correction table for the actual cable type where one is given.

4Plot it and read the shape

Plot the corrected reading of every test against time, one line per circuit, on a log scale. Insulation resistance can span several powers of ten and tends to fall by a similar proportion each year, so a steady decline shows as a near-straight line that can be extended toward the minimum. Then read the shape:

ShapeWhat it usually meansResponse
Flat, small seasonal swingSound insulation; the swing is temperature and moistureKeep the routine interval
Steady slow declineAgeing, moisture ingress or gradual damageRetest sooner, plan the repair before the alert level is reached
Sudden step downA new fault: a damaged cable, a failed joint or water in a connectorSplit the loop at the pits and find the section
Readings scatter up and downThe method is changing, or the cable ends are wet or dirtyFix the method, clean and dry the ends, repeat

5Set an alert level above the minimum

The minimum is the value below which the circuit is not acceptable, and it comes from the specification. Waiting for it is waiting for the failure, so set an alert level higher up that starts action early. A simple form is a fraction of the baseline:

Ratio = Rcorrected ÷ RbaselineIllustration: a baseline of 800 MΩ and a corrected reading of 300 MΩ give a ratio of 0.375. If the alert level is set at 0.5 of baseline, this circuit is already past it, although 300 MΩ may still be above the minimum.

The alert fraction and the minimum are set by the airport's maintenance plan and the specification, so the numbers above are only illustrations.

6What to do when the trend turns

A falling trend is a reason to test that circuit more often and to find where the loss is: isolate the circuit, split the loop at the pits and test each section, then use fault location methods if one section stands out. Treat a cable that is already trending down with care. A hi-pot test is a stress, so run it only where the specification calls for it, and do not use it to "see if it holds" on weak insulation. After a repair, take new readings and mark the change on the chart so the line is not misread later.

7Records and review

Keep the chart with the circuit's records and review it at every test, not only when a reading looks wrong. Record the measured value, the corrected value, the temperature, the conditions, the tester and the date. Continuous insulation monitoring and ground-fault detection on the CCR can add early warning between tests, but the periodic readings are what give a like-for-like history.

Diagram values are illustrative. Test voltage, reference temperature, alert level and minimum come from the specification and the airport's maintenance plan, and work follows the airport's isolation and permit-to-work rules. References: ICAO Annex 14 Vol. I Ch. 10; ICAO Doc 9157 Part 5; FAA AC 150/5340-26; IEC 61821.
Entry 12 · High-potential (hi-pot) testing Entry 14 · Photometric testing arrangement

Frequently Asked Questions

Q1Why trend the readings if the circuit already passes?

A pass only says the reading is above the minimum today. Two circuits can both pass while one is steady and the other is falling every year. The trend shows which is which, so the falling circuit can be found and repaired while it is still working, instead of after it fails.

Q2Why do readings change with the seasons?

Insulation resistance falls as the cable warms and as moisture gets into joints, cable ends and the soil around the cable. So a circuit can read lower in a hot, wet season and recover in a cool, dry one. Recording the temperature and the weather, and correcting to a reference temperature, separates this normal swing from real deterioration.

Q3Why plot the readings on a log scale?

Insulation resistance is measured in megohms and can span several powers of ten. It also tends to fall by a similar proportion each year, not by a fixed amount. On a log scale that steady fall shows as a near-straight line, which is easy to extend toward the minimum, and a sound circuit shows as a flat line.

Q4How often should insulation resistance be measured?

The interval comes from the airport's maintenance plan and the specification. A flat trend can stay on the routine interval. When the trend is falling toward the alert level, test that circuit sooner, and keep every test under the same conditions so the new points can be compared with the old.

Q5What is the difference between a slow decline and a sudden drop?

A slow decline usually points to ageing, moisture ingress or gradual damage along the cable, and gives time to plan work. A sudden step down between two tests points to a new fault, such as a damaged cable, a failed joint or water in a connector. Split the loop at the pits to find which section it is in.

Q6Do readings need to be corrected for temperature?

Yes, if the readings are to be compared over time. A common rule of thumb is that insulation resistance roughly halves for each 10 degrees C rise, but the right correction depends on the cable type. Use the correction table in the specification or from the cable maker, and record both the measured and the corrected value.

Precision AGL Academy

See It. Understand It. Then Learn How to Engineer It.

Recognising an AGL system visually is the first step. The next step is knowing how to design, install, test, commission and maintain them correctly.