How do you find a cable fault without digging up the whole route?
A failed test says the cable is faulty, not where. TDR times an echo from the fault, and bridge methods balance the loop's resistance against it. Together they turn a whole airfield route into a short stretch to pinpoint and dig.
A test such as insulation resistance or continuity (see cable testing) tells you a cable is faulty. It does not tell you where. Cable fault location works in two stages: pre-location estimates the distance to the fault from a test point, then pinpointing finds the exact spot on the ground. TDR and bridge methods are the two common pre-location tools, and both are used on a circuit that is isolated and proved dead.
1Classify the fault first
The method depends on the fault, so start with the basic tests. A continuity test that fails points to an open circuit, a broken conductor. An insulation-resistance test that fails points to an earth fault, a leak from the conductor to the ground. Note how low the fault resistance is: TDR reads open circuits and low-resistance faults well, while bridge methods suit earth faults that return only a weak echo.
2TDR: time the echo
A time-domain reflectometer sends a short, low-voltage pulse down the cable and watches for reflections. Any change in the cable's impedance sends part of the pulse back. An open circuit reflects it upward, a short or low-resistance earth fault reflects it downward, and joints and connectors show as smaller blips. The instrument times the round trip and converts it to distance:
Take Vp from the cable data, or calibrate it on a known length of the same cable, because any error in Vp is an error in the distance. TDR also has limits. A dead zone beside the instrument hides faults very close to the test end, and a high-resistance earth fault barely reflects. Faults like that may need a surge generator with an arc-reflection set, or another method, to give a usable trace; this is high-voltage work for trained staff under the site permit-to-work. On an AGL series loop every isolation transformer and connector is also a discontinuity, so the trace is busier than on a plain cable. It reads best on a section split at a pit and compared with a baseline trace recorded at commissioning.
3Bridge methods: balance the loop
A bridge compares resistances instead of timing an echo. In the Murray loop test, both ends of the isolated loop connect to two ratio arms, P and Q, the test supply goes across the two loop ends, and the junction of the arms is joined to earth through a balance detector. Adjust P:Q until the detector reads zero. The fault splits the loop into two resistances, Ra from the P end to the fault and Rb for the rest, so the balance gives the fault's position as a fraction of the loop:
The Varley loop is a refinement with an adjustable resistance in the bridge, so a second balance can be taken, which reduces reliance on an assumed loop resistance. Both methods treat the loop resistance as spread evenly along its length. A series circuit is not quite that: transformer primaries and connectors add resistance at fixed points, so convert ohms to distance using the circuit's as-built resistance schedule, not length alone.
| Method | Best for | Needs | Watch out for |
|---|---|---|---|
| TDR | Open circuits, low-resistance faults, cable length | Velocity factor; a baseline trace helps | Dead zone, high-resistance faults, echoes from transformers and joints |
| Murray loop | Earth faults that give a weak echo | Both loop ends reachable; resistance known along the loop | Transformer resistance; an unstable fault; very high fault resistance lowers the sensitivity |
| Varley loop | As Murray, with less reliance on assumed resistance | The same, plus a second balance | Follow the instrument's own procedure |
| Pinpointingacoustic or earth-gradient | The exact spot, after pre-location | Pre-location distance and route drawings | It does not measure distance from the end |
4From distance to a dig point
A distance along the cable is not yet a place on the ground. The cable follows its route with slack, bends and loops at pits and joints, so the measured length is longer than the straight-line distance. Lay the result against the as-built route drawings and the pit and marker positions. Measure from both ends if you can: the two distances should add up to the known length, and agreement is the best check that the number is right. Pinpoint on site before any excavation.
5Safety, and after the repair
Isolate the circuit, lock it out and prove it dead before anything is connected. An insulation test leaves charge in the cable, and a cable beside an energised circuit can pick up induced voltage, so discharge and earth it before handling. After the repair, retest continuity and insulation resistance, and file the fault distance, the trace and the repair record with the cable records.
Frequently Asked Questions
Q1What is the difference between pre-location and pinpointing?
Pre-location estimates the distance to the fault from a test point, using a method such as TDR or a bridge. Pinpointing then finds the exact spot on the ground, so the excavation is small. Pre-location narrows a whole route to a short stretch, and pinpointing finishes the job.
Q2Why does a TDR trace look busy on an AGL series circuit?
Every joint, connector and isolation transformer is a change in impedance, and each one sends part of the pulse back. A plain cable gives a clean trace with one echo from the fault. A series loop gives several echoes, so the trace is easiest to read on a section split at a pit and compared with a baseline trace recorded at commissioning.
Q3What is velocity factor and why does it matter?
The pulse travels along the cable at a fraction of the speed of light, and that fraction is the velocity factor, often written Vp. The instrument turns echo time into distance using it, so an error in Vp is an error in the answer by the same proportion. Take Vp from the cable data, or calibrate it on a known length of the same cable.
Q4When is a bridge method better than TDR?
When the fault is an earth fault with high resistance that returns only a weak echo. A bridge compares resistances rather than timing a reflection, so it can still balance on a fault that TDR barely sees. Very high-resistance or unstable faults may still need a different approach.
Q5Why measure from both ends of the circuit?
The two distances should add up to the known length of the cable. If they do, the number is probably right. If they do not, something is wrong, such as the wrong velocity factor, a second fault, or an error in the route records.
Q6Is it safe to connect a TDR or bridge to an AGL cable?
Only when the circuit is isolated, locked out and proved dead. An insulation test leaves charge in the cable, and a cable beside an energised circuit can pick up induced voltage, so discharge and earth it before handling. Follow the instrument manufacturer's procedure and the airport's permit-to-work rules.
See It. Understand It. Then Learn How to Engineer It.
Recognising an AGL system visually is the first step. The next step is knowing how to design, install, test, commission and maintain them correctly.
Build Practical AGL Engineering Skills
Go deeper with structured training from Precision AGL Academy, covering:
Learn how each light, sign and circuit works as part of a complete airport lighting system, not just as an isolated diagram.