Division 14 of 25 · INS-ALC Series

ALCMS & Control System Inspection

A standardized methodology for inspecting the Airfield Lighting Control and Monitoring System (ALCMS) and associated HMI, CCR remote-control interfaces, PLCs, communication networks, control cabinets, remote I/O, alarms, event logging, status feedback, and operational data. Covers workstations, HMI presentation, CCR remote control, brightness/intensity commands, alarm monitoring, event logs, communication links, PLC/interface systems, network equipment, remote equipment status, control cabinets, and system time/date synchronization.

12 / 12
Topics Published
INS-ALC-001 → 12
Inspection ID Range
Level 2
Functional · Periodic
Rev 0
Initial Issue

Critical control — command ≠ confirmation — ALCMS inspection must distinguish between command availability, command transmission, equipment response, feedback confirmation, alarm generation, and event recording. A command displayed as successful on the HMI should not automatically be treated as proof that the field equipment actually responded. If any link in the command chain fails, the system should not automatically be considered fully operational.

COMMAND TRANSMISSION FIELD RESPONSE FEEDBACK ALARM / EVENT RECORD

Division 14 · ALCMS & Control System Inspection Topics

12 of 12 topics published
INS-ALC-001 ALCMS Workstation Inspection
What's Inspected

Inspection of the ALCMS operator workstation and associated equipment, including display, input devices, power/UPS status, and alarm indication.

Inspection Points
  • Workstation condition and operation
  • Display operation, readability, status presentation
  • Keyboard/mouse and other input devices
  • Workstation power/UPS status
  • Alarm and warning indication display
  • HMI navigation, menus, and control functions
Classify As
Normal Defective Unserviceable Immediate Action Required
INS-ALC-002 HMI Status Inspection
What's Inspected

Inspection of HMI functionality and system presentation, including status display, equipment status, alarms/warnings, command interface, feedback, and navigation.

Inspection Points
  • Required AGL system status information display
  • Equipment-status indications
  • Alarm and warning display clarity
  • Command-selection and command-entry functions
  • Feedback presentation accuracy
  • Navigation to equipment/circuit pages
  • Graphic/tag identification against actual system
Classify As
Normal Defective Unserviceable Immediate Action Required
INS-ALC-003 CCR Remote-Control Inspection
What's Inspected

Inspection of communication and control between the ALCMS and CCRs, including remote status, remote commands, and alarm/communication-failure indication.

Inspection Points
  • CCR operating status displayed correctly
  • Remote CCR control functions
  • Intensity-step commands
  • Command-feedback correspondence with commanded state
  • CCR alarms communicated to ALCMS
  • Indication when communication with a CCR is interrupted
Classify As
Normal Defective Unserviceable Immediate Action Required
INS-ALC-004 Brightness-Command Verification
What's Inspected

Verification of applicable AGL lighting intensity commands from the ALCMS, from selection through transmission, feedback, and actual lighting response.

Inspection Points
  • Intensity levels correctly displayed and selectable
  • Command transmission to intended control equipment
  • Resulting equipment status/feedback correspondence
  • Commanded vs. reported-state mismatch identification
  • Lighting-response verification via approved procedures
Classify As
Normal Defective Unserviceable Immediate Action Required
INS-ALC-005 Alarm-Monitoring Inspection
What's Inspected

Inspection of alarm-monitoring functionality, including generation, display, acknowledgement, reset, priority, source identification, and history.

Inspection Points
  • Alarm generation for applicable abnormal conditions
  • Alarm visibility and identification
  • Alarm-acknowledgement functionality
  • Alarm-reset functionality
  • Alarm priority against approved configuration
  • Correct equipment/circuit/source identification
  • Alarm-history records and recurring/intermittent alarms
Classify As
Normal Defective Unserviceable Immediate Action Required
INS-ALC-006 Event-Log Inspection
What's Inspected

Inspection of ALCMS event recording, timestamps, and required operational data logging, including retention and record integrity.

Inspection Points
  • Event recording and appropriate date/time information
  • Operator command recording
  • Equipment-status change recording
  • Alarm recording in event history
  • Event sequence for selected abnormal/operational events
  • Historical event/data retention and record integrity
Classify As
Normal Defective Unserviceable Immediate Action Required
INS-ALC-007 Communication-Link Inspection
What's Inspected

Inspection of communication paths between ALCMS components, CCR equipment, and remote I/O, including status, loss/restoration handling, and fault history.

Inspection Points
  • Communication paths between ALCMS components
  • Communication with CCR equipment and remote I/O
  • Communication-status indications
  • Communication-loss alarm generation
  • Communication-restoration detection/recording
  • Recurring communication-fault history
Classify As
Normal Defective Unserviceable Immediate Action Required
INS-ALC-008 PLC/Interface Inspection
What's Inspected

Inspection of applicable PLC status and physical condition, and the interfaces between PLCs and associated control/monitoring equipment.

Inspection Points
  • PLC power/status indications
  • PLC fault indications and diagnostics
  • Input status
  • Output status
  • Interfaces to associated control/monitoring equipment
  • PLC communication status
  • Diagnostic and fault-history records
Classify As
Normal Defective Unserviceable Immediate Action Required
INS-ALC-009 Network-Equipment Inspection
What's Inspected

Inspection of applicable network equipment supporting the control system, including switches, links, ports, cabling, and power status.

Inspection Points
  • Switch status and fault indications
  • Network-link status
  • Network-port status (where accessible and authorized)
  • Accessible network cables and connections
  • Network-equipment power status
  • Recurring network faults and communication interruptions
Classify As
Normal Defective Unserviceable Immediate Action Required
INS-ALC-010 Remote-Equipment-Status Inspection
What's Inspected

Verification that field equipment status is correctly reported at the ALCMS, including availability, command/feedback comparison, and fault indication.

Inspection Points
  • Field equipment status reporting accuracy
  • Communication and availability status
  • Commanded state vs. reported equipment state
  • Remote-equipment fault identification
  • Indication when remote equipment becomes unavailable
Classify As
Normal Defective Unserviceable Immediate Action Required
INS-ALC-011 Control-Cabinet Inspection
What's Inspected

Inspection of ALCMS control cabinets for physical and operational condition, including access, internal wiring, earthing, and cleanliness.

Inspection Points
  • Doors, locks, hinges, access arrangements
  • Accessible internal components (authorized personnel)
  • Control wiring and termination condition
  • Terminals and connections
  • Cabinet earthing/bonding
  • Cooling/ventilation arrangements
  • Dust, contamination, moisture, foreign material
  • Component and wiring identification/labels
Classify As
Normal Defective Unserviceable Immediate Action Required
INS-ALC-012 System Time/Date Verification
What's Inspected

Verification of ALCMS system time and date, synchronization across system components, and the accuracy of event/alarm timestamps.

Inspection Points
  • System time verification
  • System date verification
  • Time synchronization between ALCMS, PLCs, servers, workstations
  • Event and alarm timestamp accuracy
  • Time discrepancies between system components
Classify As
Normal Defective Unserviceable Immediate Action Required
No topics match your search.

Division-Wide Requirements

Common classification scheme, workflow and records that apply across all 12 Division 14 inspection topics.

A. Standard Inspection Classification

Every observation should be assigned an appropriate status:

NormalEquipment/condition satisfactory and operating as expected.

DefectiveAbnormality or defect identified but equipment remains operational or condition does not require immediate withdrawal.

UnserviceableEquipment or system is not available for its intended function.

Immediate Action RequiredCondition presents an operational, electrical, safety, or airside risk requiring immediate escalation/action.

B. Standard Inspection Workflow

The following sequence applies across all Division 14 topics:

CHECK ALCMS AVAILABILITY INSPECT WORKSTATION INSPECT HMI CHECK EQUIPMENT STATUS VERIFY COMMANDS VERIFY CCR REMOTE CONTROL VERIFY BRIGHTNESS/INTENSITY COMMANDS VERIFY FEEDBACK CHECK ALARMS CHECK EVENT LOGS CHECK COMMUNICATION CHECK PLC CHECK NETWORK CHECK REMOTE EQUIPMENT STATUS INSPECT CONTROL CABINETS VERIFY DATE/TIME CHECK DATA LOGGING REVIEW FAULT HISTORY CLASSIFY DEFECT RECORD CORRECT FUNCTIONAL VERIFICATION CLOSE

C. Minimum Inspection Record

Each inspection record should include:

  • Date and inspection time
  • Inspector name and designation
  • ALCMS/workstation/component identification
  • Affected equipment/circuit reference
  • Inspection observation per topic
  • Command/feedback comparison result, where applicable
  • Status classification
  • Defect description, where applicable
  • Immediate action taken
  • Person/department notified
  • Corrective-action reference
  • Closure date/time
  • Inspector's verification/sign-off

D. Scope Boundary

ALCMS & control system inspection is intended to

  • Verify the operational, communication, monitoring, and control condition of the ALCMS, HMI, CCR remote-control interfaces, PLCs, communication networks, control cabinets, remote I/O, alarms, event logging, and operational data.

It does not replace

  • Cybersecurity assessment
  • PLC programming/logic verification
  • Detailed network engineering diagnostics
  • Photometric testing of the fed lighting
  • Electrical testing of field equipment
  • Software/firmware update and change-management procedures

Frequently Asked Questions

Quick answers about alcms & control system inspection in the AGL Inspection Handbook.

Q1What is Division 14 — ALCMS & Control System Inspection in the AGL Inspection Handbook?

Division 14 contains 12 published topics (Level 2, functional and periodic). It gives a standardized methodology for inspecting the Airfield Lighting Control and Monitoring System (ALCMS) and its HMI, CCR remote-control interfaces, PLCs, communication networks, control cabinets, remote I/O, alarms, event logging, status feedback and operational data.

Q2What does the ALCMS inspection cover?

It covers workstations, HMI presentation, CCR remote control, brightness and intensity commands, alarm monitoring, event logs, communication links, PLC and interface systems, network equipment, remote equipment status and control cabinets.

Q3What is the ALCMS inspection workflow?

The sequence checks ALCMS availability, inspects the workstation and HMI, and checks equipment status. It then verifies commands, CCR remote control, brightness and intensity commands and feedback, checks alarms, event logs, communication, PLC, network and remote equipment status, inspects control cabinets, verifies date and time, and checks data logging and fault history. It ends with classify defect, record, correct, functional verification and close.

Q4What status classifications are used in this division?

Every observation is assigned one of four statuses. Normal means the equipment or condition is satisfactory and operating as expected. Defective means an abnormality or defect exists but the equipment remains operational or the condition does not require immediate withdrawal. Unserviceable means the equipment or system is not available for its intended function. Immediate Action Required means the condition presents an operational, electrical, safety or airside risk requiring immediate escalation and action.

Q5What extra information does an ALCMS inspection record include?

Alongside the usual date, inspector, observation, status, action and sign-off fields, the record includes the ALCMS, workstation or component identification, the affected equipment or circuit reference, and the command and feedback comparison result where applicable.

Q6Does the ALCMS inspection replace cybersecurity or PLC verification?

No. It does not replace cybersecurity assessment, PLC programming or logic verification, detailed network engineering diagnostics, photometric testing of the fed lighting, electrical testing of field equipment, or software/firmware update and change-management procedures.

Q7Do airport procedures take precedence over this handbook?

Yes. This handbook is an uncontrolled educational reference, not an approved procedure. The airport's approved inspection schedule, SMS procedures, ATC instructions, NOTAM procedures and local aerodrome regulations always take precedence, and the current revision of any official document should be verified before use.

Q8Can I download a printable checklist for each inspection topic?

Yes. Each inspection topic has a Download as Word option that produces an uncontrolled Word checklist template (description, a tick-box inspection table and an inspector sign-off block) for personal reference and internal training, to be reviewed and adopted under the user’s own document control.

Precision AGL Academy

Don't Just Inspect the Control System. Understand the System.

ALCMS and control-system inspection is where monitoring, sequencing and interlock condition awareness begins. Go beyond identifying defects and build the technical knowledge to understand why abnormalities occur, how they affect system serviceability, and when further testing, troubleshooting, maintenance or corrective action is required.

Build Practical AGL Inspection & Maintenance Capability

Develop structured knowledge across:

AGL Fundamentals Components Inspection Electrical Systems Photometry Testing Troubleshooting Maintenance Commissioning

Learn to connect the inspection process with the wider AGL engineering lifecycle.

Inspect with purpose. Understand the system. Act with technical confidence.