Division 15 of 25 · Failure Database

Earthing & Bonding Failures

The dedicated failure-classification section for AGL earthing, bonding, earth-electrode and lightning/surge-protection infrastructure — covering failures from the main earth network through individual AGL assets, including fixtures, isolating transformers, airfield signs, CCRs, panels and earth pits. Do not record an earthing or bonding fault simply as “earth fault.” Identify the failure mode, electrical condition, physical evidence, probable cause, root cause, corrective action and recurrence risk.

18 / 18
Topics Published
EBF-01 → 18
Failure ID Range
6 Groups
Electrical Performance · Conductor & Connection · Equipment Bonding · Pit & Electrode · Lightning & Surge · Installation
Rev 0
Initial Issue

Key principle — An earthing or bonding failure should be recorded separately from the equipment failure that it causes. For example: loose earth connection → poor bonding → high earth resistance/earth continuity problem → equipment safety risk. Every record should answer: what failed → how did it fail → why did it fail → what evidence confirmed it → how was it corrected → how can recurrence be prevented?

Division 15 · Earthing & Bonding Failure Topics

18 of 18 topics published
A
Earth Electrical Performance
2 topics
EBF-01 High Earth Resistance
Failure Definition

Measured earth resistance is higher than the applicable design, project, maintenance or acceptance requirement.

Possible Causes
  • Earth-electrode deterioration
  • Poor soil contact
  • Corrosion
  • Loose connection
  • Broken earth conductor
  • Inadequate earthing installation
  • Earth-pit deterioration
Possible Consequences
  • Ineffective fault-current path
  • Increased touch/step potential risk
  • Reduced protection effectiveness
  • Poor lightning/surge discharge path
Investigation
  • Earth resistance measurement
  • Earth conductor
  • Earth connections
  • Earth electrode
  • Earth pit
  • Corrosion
  • Bonding connections
  • Test records/trend history
Failure Chain
EARTH-ELECTRODE DETERIORATIONINCREASING EARTH RESISTANCEHIGH EARTH RESISTANCEREDUCED EARTHING-SYSTEM EFFECTIVENESS
EBF-02 Earth Continuity Failure
Failure Definition

The required electrical continuity of the earthing conductor/bonding path is not maintained.

Possible Causes
  • Broken conductor
  • Loose connection
  • Corrosion
  • Missing bonding link
  • Damaged terminal
  • Incorrect installation
Consequences
  • Equipment may become inadequately bonded
  • Fault-current path may be compromised
  • Protection performance may be affected
Investigation

Verify continuity from the relevant equipment to the designated earthing point/network.

Failure Chain
BROKEN CONDUCTOREARTH CONTINUITY FAILUREEQUIPMENT BONDING FAILURE
B
Earth Conductor & Connection Failures
5 topics
EBF-03 Broken Earth Conductor
Failure Definition

Physical or electrical discontinuity of an earth conductor.

Possible Causes
  • Mechanical damage
  • Corrosion
  • Excavation/construction damage
  • Improper installation
  • Ageing
  • Termination failure
Consequences
  • Earth continuity failure
  • Equipment bonding failure
  • Potential safety hazard
Investigation
  • Conductor route
  • Physical condition
  • Terminations
  • Joints
  • Continuity
Failure Chain
MECHANICAL DAMAGEBROKEN EARTH CONDUCTOREARTH CONTINUITY FAILUREEQUIPMENT BONDING FAILURE
EBF-04 Loose Earth Connection
Failure Definition

Earth conductor or bonding connection is not securely connected to its designated termination.

Possible Causes
  • Improper tightening
  • Vibration
  • Poor installation
  • Thermal cycling
  • Mechanical disturbance
Consequences
  • High contact resistance
  • Intermittent earth continuity
  • Poor bonding
  • Potential overheating at the connection
Corrective Action

Inspect, clean where appropriate, correctly secure and verify the connection according to the applicable procedure/specification.

Failure Chain
LOOSE EARTH CONNECTIONPOOR BONDINGEARTH CONTINUITY DEGRADATIONPROTECTION/SAFETY-PATH DEGRADATION
EBF-05 Corroded Earth Connection
Failure Definition

Corrosion has degraded an earth/bonding connection sufficiently to affect its electrical or mechanical integrity.

Possible Causes
  • Moisture
  • Salt exposure
  • Environmental corrosion
  • Poor protective treatment
  • Ageing
Consequences
  • Increased resistance
  • Loss of continuity
  • Weak bonding
  • Eventual open circuit
Investigation
  • Connection
  • Lug/terminal
  • Conductor
  • Contact surface
  • Corrosion severity
Failure Chain
MOISTURE/SALT EXPOSURECORRODED EARTH CONNECTIONINCREASED RESISTANCEHIGH EARTH RESISTANCEEARTHING-SYSTEM DEGRADATION
EBF-06 Poor Bonding
Failure Definition

Bonding between conductive components/equipment is inadequate to maintain the intended equipotential and electrical connection.

Possible Causes
  • Loose connection
  • Corrosion
  • Incorrect bonding conductor
  • Missing bonding point
  • Poor installation
  • Inadequate contact surface
Consequences
  • Potential differences between conductive parts
  • Poor fault-current path
  • Equipment safety risk
  • Increased susceptibility to transient events
Failure Chain
LOOSE EARTH CONNECTIONPOOR BONDINGEARTH CONTINUITY DEGRADATIONPROTECTION/SAFETY-PATH DEGRADATION
EBF-07 Missing Bonding Connection
Failure Definition

A required bonding connection is absent.

Possible Causes
  • Installation omission
  • Maintenance error
  • Modification without restoration
  • Damaged/removed bonding conductor
  • Incorrect installation
Investigation

Compare the installed bonding arrangement against the approved design/installation requirement.

Important Distinction

Missing bonding connection is the failure mode. Poor bonding is the condition resulting from inadequate bonding.

C
Equipment Bonding Failures
5 topics
EBF-08 Fixture Bonding Failure
Failure Definition

Failure or absence of the required bonding connection associated with an AGL light fixture.

Potential Causes
  • Broken bonding conductor
  • Loose terminal
  • Corrosion
  • Incorrect installation
  • Missing bonding connection
Investigation
  • Fixture body
  • Bonding conductor
  • Terminal
  • Connection point
  • Continuity
Cross-Reference

Cross-reference with Division 01 — Lighting Fixture Failures.

EBF-09 Transformer Bonding Failure
Failure Definition

Failure of the required bonding arrangement associated with an isolation transformer or transformer installation.

Possible Causes
  • Loose connection
  • Corrosion
  • Broken conductor
  • Missing bonding connection
  • Incorrect installation
Investigation

Verify the intended bonding path and its continuity.

Cross-Reference

Cross-reference with Division 04 — Isolation Transformer Failures.

EBF-10 Sign Bonding Failure
Failure Definition

Failure of the required bonding arrangement associated with an illuminated airfield sign and its supporting/electrical components.

Possible Causes
  • Loose connection
  • Corrosion
  • Broken bonding conductor
  • Missing bond
  • Incorrect installation
Consequences
  • Loss of intended equipotential bonding
  • Safety risk
  • Potential electrical fault-path degradation
Cross-Reference

Cross-reference with Division 12 — Airfield Sign Failures.

EBF-11 CCR Earth Failure
Failure Definition

Failure of the required earthing arrangement associated with a Constant Current Regulator.

Possible Causes
  • Broken earth conductor
  • Loose terminal
  • Corrosion
  • Incorrect installation
  • Earth continuity failure
Investigation
  • CCR earth terminal
  • Earth conductor
  • Panel connections
  • Earth continuity
  • Earth resistance where applicable
  • Associated earth network
Cross-Reference

Cross-reference with Division 03 — CCR Failures.

EBF-12 Panel Earth Failure
Failure Definition

Failure of the earthing arrangement associated with an electrical/control panel.

Possible Causes
  • Loose earth terminal
  • Broken conductor
  • Corrosion
  • Missing connection
  • Incorrect wiring
Consequences
  • Loss of intended panel bonding
  • Safety risk
  • Protection-path degradation
Investigation

Check: Panel body → earth terminal → earth conductor → earth network.

Cross-Reference

Cross-reference with Division 02 — Electrical Failures.

D
Earth-Pit & Electrode Failures
2 topics
EBF-13 Earth-Pit Deterioration
Failure Definition

Deterioration of the earth pit or associated components affecting the integrity or accessibility of the earthing system.

Possible Causes
  • Corrosion
  • Water ingress/accumulation
  • Physical deterioration
  • Damaged cover
  • Environmental degradation
  • Poor maintenance
Inspection Points
  • Earth-pit condition
  • Cover
  • Connections
  • Conductors
  • Electrode connection
  • Corrosion
  • Water accumulation
  • Accessibility for testing
EBF-14 Earth-Electrode Deterioration
Failure Definition

Deterioration of the earth electrode resulting in degradation of the earthing system.

Possible Causes
  • Corrosion
  • Ageing
  • Environmental exposure
  • Physical damage
  • Deterioration of electrode connections
Possible Consequences
  • Increasing earth resistance
  • Poor fault-current path
  • Reduced lightning/surge discharge effectiveness
Reliability Principle

Earth-electrode resistance should be trended over time, rather than relying only on a single measurement.

E
Lightning & Surge Protection
2 topics
EBF-15 Lightning-Protection Failure
Failure Definition

Failure or degradation of the lightning-protection arrangement associated with the AGL installation.

Possible Causes
  • Broken conductor
  • Poor bonding
  • Corrosion
  • Damaged connection
  • Incorrect installation
  • Structural damage
Potential Consequences
  • Inadequate lightning-current path
  • Increased equipment exposure
  • Increased risk of damage to AGL electrical/electronic equipment
Investigation
  • Lightning conductors
  • Bonding
  • Earth connections
  • Earth electrodes
  • Connection integrity
  • Physical damage
  • Previous lightning-event history
EBF-16 Surge-Protection Failure
Failure Definition

Failure or degradation of surge-protection equipment or its associated earthing/bonding path.

Possible Causes
  • Surge event
  • SPD degradation/failure
  • Poor earth connection
  • Incorrect installation
  • Loss of bonding
  • End-of-life condition
Consequences
  • Reduced transient protection
  • Increased exposure of CCR/control/AGL equipment to electrical surges
Important Diagnostic Principle

A surge-protection device should not be assessed independently of its earthing and bonding path.

Failure Chain
POOR EARTH/BONDING PATHSURGE-PROTECTION DEGRADATIONREDUCED TRANSIENT-CURRENT DISCHARGE PATHINCREASED EQUIPMENT EXPOSURE
F
Installation & Consequential Failures
2 topics
EBF-17 Incorrect Earthing Installation
Failure Definition

Earthing system has been installed in a manner that does not conform to the approved design, applicable specification or installation procedure.

Examples
  • Incorrect connection point
  • Incorrect conductor arrangement
  • Missing earth connection
  • Incorrect termination
  • Incorrect electrode arrangement
  • Incorrect bonding
Possible Consequences
  • High earth resistance
  • Earth continuity failure
  • Poor bonding
  • Equipment protection failure
Investigation

Compare: Approved design → installation → inspection/testing records → measured results.

Failure Chain
INCORRECT EARTHING INSTALLATIONMISSING/INCORRECT BONDINGPOOR BONDINGEARTH CONTINUITY/RESISTANCE PROBLEMPOTENTIAL EQUIPMENT/PROTECTION FAILURE
EBF-18 Earth Fault Due to Poor Bonding
Failure Definition

An electrical earth fault or abnormal condition is associated with inadequate or defective bonding.

Possible Causes
  • Missing bonding
  • Loose bonding
  • Corroded bonding
  • Broken conductor
  • Incorrect installation
Investigation

Determine: fault location, bonding condition, earth continuity, conductor condition, connection resistance, equipment affected, root cause.

Important Classification

Do not record only “earth fault.” Where evidence establishes defective bonding as the underlying mechanism, record “earth fault due to poor bonding” and identify the specific bonding failure separately.

No topics match your search.

Division-Wide Requirements

Standard record structure, failure-chain relationships, diagnostic matrix, asset-based tracing, RCA linkage, evidence layer and severity scheme that apply across all 18 Division 15 failure topics.

A. Asset-Specific Earthing Failure Trace

The Division allows failures to be traced to individual AGL assets, from the main earth network through to the individual bonding point:

RUNWAY/TAXIWAY FIXTUREBONDING CONDUCTOREARTH NETWORK
ISOLATION TRANSFORMER ENCLOSURE/EARTH POINTBONDINGEARTH NETWORK
AIRFIELD SIGN STRUCTURE/ELECTRICAL EARTHBONDINGEARTH NETWORK
CCR ENCLOSUREEARTH TERMINALEARTH NETWORK
PANEL BODYEARTH TERMINALEARTH CONDUCTOREARTH NETWORK
EARTH CONNECTIONELECTRODESURROUNDING EARTH

This asset-based approach makes the failure database useful for inspection, troubleshooting, maintenance and reliability analysis.

B. Recommended Division 15 Failure Record

Every Division 15 failure should ideally be converted into a standard failure record with the following fields:

Asset Identification

  • Failure ID
  • Airport
  • Location
  • Asset ID
  • Asset Type
  • Circuit ID
  • Earth-System Reference
  • Date/Time

Electrical Condition

  • Failure Category
  • Failure Mode
  • Earth Resistance
  • Earth Continuity
  • Bonding Condition
  • Connection Condition
  • Conductor Condition

Physical Condition

  • Corrosion
  • Earth-Pit Condition
  • Electrode Condition
  • Mechanical Damage
  • Water/Moisture Condition

Protection

  • Lightning-Protection Condition
  • Surge-Protection Condition
  • Bonding Arrangement
  • Protection-Path Condition

Installation

  • Installation Compliance
  • Drawing/Design Reference
  • Previous Modification
  • Maintenance History

RCA

  • Immediate Cause
  • Failure Mechanism
  • Contributing Factor
  • Root Cause

Corrective Action

  • Connection Repair
  • Conductor Replacement
  • Bonding Restoration
  • Corrosion Treatment
  • Earth-Pit Repair
  • Electrode Repair/Replacement
  • Lightning Protection Repair
  • Surge Protection Repair
  • Installation Correction

Verification & Reliability

  • Earth Continuity Test
  • Earth Resistance Test
  • Bonding Verification
  • Visual Inspection
  • Lightning-Protection Verification
  • Surge-Protection Verification
  • Final Acceptance
  • Return to Service
  • Previous Failure
  • Repeat Occurrence
  • Resistance Trend
  • Corrective Action Effectiveness
  • Preventive Action
  • Lessons Learned

C. Failure-Chain Relationships

Division 15 becomes much more valuable when the database captures relationships between failure modes rather than treating each as isolated.

Chain 1 — Connection
LOOSE EARTH CONNECTIONPOOR BONDINGEARTH CONTINUITY DEGRADATIONPROTECTION/SAFETY-PATH DEGRADATION
Chain 2 — Corrosion
MOISTURE/SALT EXPOSURECORRODED EARTH CONNECTIONINCREASED RESISTANCEHIGH EARTH RESISTANCEEARTHING-SYSTEM DEGRADATION
Chain 3 — Broken Conductor
MECHANICAL DAMAGEBROKEN EARTH CONDUCTOREARTH CONTINUITY FAILUREEQUIPMENT BONDING FAILURE
Chain 4 — Earth Electrode
EARTH-ELECTRODE DETERIORATIONINCREASING EARTH RESISTANCEHIGH EARTH RESISTANCEREDUCED EFFECTIVENESS OF EARTHING SYSTEM
Chain 5 — Incorrect Installation
INCORRECT EARTHING INSTALLATIONMISSING/INCORRECT BONDINGPOOR BONDINGEARTH CONTINUITY/RESISTANCE PROBLEMPOTENTIAL EQUIPMENT/PROTECTION FAILURE
Chain 6 — Surge Protection
POOR EARTH/BONDING PATHSURGE-PROTECTION DEGRADATIONREDUCED TRANSIENT-CURRENT DISCHARGE PATHINCREASED EQUIPMENT EXPOSURE

D. Earthing & Bonding Diagnostic Matrix

FailurePrimary Investigation
High earth resistanceEarth resistance measurement/trend
Earth continuity failureContinuity path
Broken earth conductorConductor condition
Loose earth connectionConnection integrity
Corroded earth connectionCorrosion/contact condition
Poor bondingBonding integrity
Missing bonding connectionDesign vs installed bond
Fixture bonding failureFixture bond/continuity
Transformer bonding failureTransformer bond/continuity
Sign bonding failureSign bond/continuity
CCR earth failureCCR earth path
Panel earth failurePanel earth path
Earth-pit deteriorationPit/connection condition
Earth-electrode deteriorationElectrode condition/resistance
Lightning-protection failureLightning/bonding network
Surge-protection failureSPD + earth path
Incorrect earthing installationDesign/installation verification
Earth fault due to poor bondingFault + bonding RCA

E. RCA Connection

Division 15 links every failure to the Root Cause Analysis Database. The most relevant RCA categories for earthing and bonding failures are:

ElectricalCorrosionMechanicalEnvironmentalInstallationMaintenanceDesignMaterialComponentHumanProceduralOperationalUnknown/Pending

F. Failure Severity

Every failure receives a severity classification, plus operational-impact tagging:

Critical / Safety-Critical — immediate operational or safety risk

Major / Operationally Critical — significant availability impact

Moderate — reduced performance, not yet critical

Minor / Non-Critical — limited or no operational effect

Degradation / Intermittent / Latent — developing or hidden fault

G. Evidence Layer

Visual evidence

  • Earth-pit, cover and electrode photographs
  • Connection, lug/terminal and bonding-point photographs
  • Corrosion, water-ingress and mechanical-damage photographs

Technical evidence

  • Earth resistance measurement and trend history
  • Earth continuity test results
  • Lightning/surge-protection test and inspection records, maintenance history

H. Failure → RCA → Action → Reliability Loop

Every earthing/bonding failure should eventually become engineering intelligence:

FAILURE EVENT FAILURE MODE FAILURE MECHANISM ROOT CAUSE CORRECTIVE ACTION PREVENTIVE ACTION POST-REPAIR TEST

For example: High earth resistance reading → traced to electrode deterioration → corrosion of electrode connection → environmental exposure → electrode repair/replacement → review protective treatment → post-repair earth resistance test.

Failure Database vs. Troubleshooting Atlas

The Troubleshooting Atlas answers “I have a fault now — how do I diagnose and fix it?” The Failure Database answers “this failure happened — what happened, why, what evidence proves it, what was done, and how do we stop it recurring?” Kept strictly separate, then linked end-to-end, the two form a genuine AGL Failure Intelligence Engine rather than a simple fault list. Division 15 connects directly with Division 01 Lighting Fixture Failures, Division 02 Electrical Failures, Division 03 CCR Failures, Division 04 Isolation Transformer Failures, Division 12 Airfield Sign Failures, Division 18 Maintenance-Induced Failures, Division 19 Product & Component Reliability, Division 21 RCA and Division 23 Reliability Trend Analysis.

Frequently Asked Questions

Quick answers about AGL earthing, bonding and surge-protection failures, as covered in Division 15 of the AGL Failure Database.

Q1What is Division 15 — Earthing & Bonding Failures in the AGL Failure Database?

Division 15 covers AGL earthing, bonding, earth-electrode and lightning or surge-protection failures. It contains 18 published topics (EBF-01 to EBF-18), including high earth resistance, earth continuity failure, broken earth conductor, poor bonding and lightning and surge protection failure.

Q2Which earthing and bonding failures does Division 15 cover?

High earth resistance, earth continuity failure, broken earth conductor, loose earth connection, corroded earth connection, poor bonding, missing bonding connection, fixture, transformer and sign bonding failure, CCR earth failure, panel earth failure, earth-pit and earth-electrode deterioration, lightning-protection failure, surge-protection failure, incorrect earthing installation and earth fault due to poor bonding.

Q3How are the 18 earthing and bonding topics grouped?

They fall into six groups: Earth Electrical Performance (2 topics), Earth Conductor & Connection Failures (5), Equipment Bonding Failures (5), Earth-Pit & Electrode Failures (2), Lightning & Surge Protection (2) and Installation & Consequential Failures (2).

Q4How can an earthing failure be traced to a specific AGL asset?

Division 15 lets failures be traced from the main earth network to the individual bonding point. Traces run from a runway or taxiway fixture through its bonding conductor, from an isolation transformer enclosure earth point, from an airfield sign structure bond, from a CCR enclosure earth terminal and from a panel body earth terminal, each back to the earth network, and finally from the earth connection and electrode to the surrounding earth.

Q5What earthing failure chains does Division 15 capture?

In the connection chain, a loose earth connection leads to poor bonding, earth continuity degradation and degradation of the protection or safety path. In the corrosion chain, moisture or salt exposure leads to a corroded earth connection, increased resistance, high earth resistance and earthing-system degradation.

Q6Where should the investigation start for an earthing or bonding failure?

The diagnostic matrix assigns a primary investigation to each topic. High earth resistance starts with earth-resistance measurement and trend, earth continuity failure with the continuity path, broken earth conductor with conductor condition, loose earth connection with connection integrity, corroded earth connection with corrosion and contact condition, poor bonding with bonding integrity, and missing bonding connection with design versus installed bond.

Q7How does an earthing failure become engineering intelligence?

Every failure follows a loop: failure event, failure mode, failure mechanism, root cause, corrective action, preventive action and post-repair test. For example, a high earth-resistance reading is traced to electrode deterioration, then to corrosion of the electrode connection caused by environmental exposure, leading to electrode repair or replacement.

Q8How are failure severity and operational impact classified?

Every failure receives a severity classification, plus operational-impact tagging. The classes are Critical / Safety-Critical (immediate operational or safety risk), Major / Operationally Critical (significant availability impact), Moderate (reduced performance, not yet critical), Minor / Non-Critical (limited or no operational effect), and Degradation / Intermittent / Latent (a developing or hidden fault).

Q9How does the Failure Database differ from the Troubleshooting Atlas?

The Troubleshooting Atlas answers “I have a fault now — how do I diagnose and fix it?” The Failure Database answers “this failure happened — what happened, why, what evidence proves it, what was done, and how do we stop it recurring?” Kept strictly separate, then linked end to end, the two form an AGL Failure Intelligence Engine rather than a simple fault list.

Beyond the Failed Megger Test

DON’T JUST RETEST THE EARTH. UNDERSTAND THE BONDING SYSTEM.

A high resistance reading can come from a corroded electrode, a broken bonding connection, soil conditions or a design gap — real troubleshooting means understanding the earthing and bonding system well enough to trace the reading back to its cause.

Take that knowledge further with Precision AGL Academy.

Build Practical AGL Troubleshooting Skills

Learn how to connect:

Failure Symptoms System Understanding Investigation Root Cause Corrective Action Verification Recurrence Prevention

Develop structured knowledge across AGL fundamentals, components, electrical systems, testing, photometry, troubleshooting, maintenance and commissioning.

Find the failure. Understand the cause. Build the engineering skill.

Talk to Precision AGL Academy

Follow the Academy