Stop Bar (SPB) and Runway Guard Light (GRD) fault diagnosis — from a dark or partially illuminated stop bar through to flicker, wrong-colour and intensity compliance, local control, safety interlock and remote command faults, series circuit, connector and transformer failure on the stop bar side; and guard light illumination, colour, intermittent, and flash-controller faults on the runway guard light side. Each topic follows the full engineering diagnostic record: symptom → observation → measurement → decision → fault location → root cause → verification → corrective action → preventive action.
Symptom — A stop bar (or the full set of fixtures spanning the taxiway at the CAT II/III holding position) is commanded ON from ALCMS/ATC but fails to illuminate.
Stop bar fixtures — in-pavement or elevated red L-852E lights spanning the taxiway at the CAT II/III holding position, fed via a dedicated stop bar series circuit and isolation transformers, commanded ON/OFF from the ALCMS/ATC control panel.
Confirm the stop bar illuminates correctly at commanded ON, and confirm the interlock correctly inhibits the downstream centreline lighting while the bar is lit, before returning to automatic control.
SOP: SOP-SPB-01 (Stop Bar Fault Isolation Procedure), SOP-CCR-04 (CCR LOTO Procedure)
Standards: ICAO Annex 14 Vol I (stop bar requirements), FAA AC 150/5340-30, FAA AC 150/5345-46 (L-852E)
Diagram: Stop Bar Circuit & Interlock Layout Drawing
Case Study: Division 01 — CCR Troubleshooting; Division 24 — Complete Runway Lighting Failure
Symptom — One or more individual fixtures within an otherwise correctly energised stop bar fail to illuminate, while the remainder of the bar lights normally.
Individual stop bar fixture positions within the bar, and the series circuit segment feeding them.
Re-energise and confirm every fixture in the bar illuminates uniformly at the commanded intensity step.
SOP: SOP-SPB-01 (Stop Bar Fault Isolation Procedure)
Standards: ICAO Annex 14 Vol I, FAA AC 150/5345-46
Diagram: Stop Bar Fixture Layout Drawing
Case Study: Division 25 — Field Case Study Troubleshooting
Symptom — One or more stop bar fixtures flicker, pulse, or vary in brightness instead of holding a steady red output at the commanded state.
Stop bar fixture, isolation transformer, connector, and the interlock relay/logic governing the circuit.
Monitor the repaired fixture over several operating cycles, including interlock transitions, before closing out.
SOP: SOP-SPB-01 (Stop Bar Fault Isolation Procedure), SOP-SPB-03 (Interlock Function Test Procedure)
Standards: ICAO Annex 14 Vol I, FAA AC 150/5345-46
Diagram: Stop Bar Circuit & Interlock Layout Drawing
Case Study: Division 01 — CCR Troubleshooting
Symptom — A stop bar fixture displays a colour other than red, creating a safety-critical guidance discrepancy at a CAT II/III holding position.
Stop bar fixture lens/filter assembly and lamp/LED colour source.
Re-check chromaticity after correction and confirm visually against the other fixtures in the same stop bar at night.
SOP: SOP-SPB-04 (Colour Verification Procedure)
Standards: ICAO Annex 14 Vol I (colour specifications), FAA AC 150/5345-46
Diagram: Stop Bar Fixture Layout Drawing
Case Study: Division 26 — Photometric & Intensity Compliance
Symptom — A photometric survey or reported observation finds the stop bar, or a section of it, below the minimum required intensity for its operating category.
Stop bar fixture photometric output as measured against ICAO Annex 14 Appendix 2 / FAA AC 150/5340-30 specifications.
Conduct a follow-up photometric survey of the corrected fixtures, and cross-check a sample of unaffected fixtures to confirm the survey and correction are consistent.
SOP: SOP-SPB-05 (Photometric Compliance Survey Procedure)
Standards: ICAO Annex 14 Vol I Appendix 2, FAA AC 150/5340-30
Diagram: Stop Bar Photometric Specification Sheet
Case Study: Division 26 — Photometric & Intensity Compliance
Symptom — The stop bar's local control system fails to correctly execute an ON/OFF command, or reports a status to ALCMS that does not match the actual field state.
Stop bar local control system — the CCR-integrated or standalone controller/PLC card, selector relays, and status feedback circuitry that executes ON/OFF commands and reports stop bar status to ALCMS.
Command the stop bar ON/OFF several times from ALCMS and confirm both the actual field state and the reported status match on each cycle.
SOP: SOP-SPB-06 (Stop Bar Control System Test Procedure)
Standards: ICAO Annex 14 Vol I, FAA AC 150/5340-30
Diagram: Stop Bar Control Cabinet Wiring Diagram
Case Study: Division 01 — CCR Troubleshooting
Symptom — The safety interlock between the stop bar and the downstream taxiway centreline lighting fails to prevent both from being illuminated simultaneously, or fails to allow the centreline lighting to activate when the stop bar is correctly switched OFF.
Stop bar / taxiway centreline interlock logic — the control circuitry (relay-based or PLC-based) that ensures the stop bar and the taxiway centreline lighting beyond it are never illuminated simultaneously, per ICAO Annex 14 Vol I requirements for CAT II/III holding positions.
Run a complete interlock test cycle — stop bar ON/centreline OFF, then stop bar OFF/centreline ON — and confirm correct mutually exclusive operation before returning to automatic control.
SOP: SOP-SPB-03 (Interlock Function Test Procedure)
Standards: ICAO Annex 14 Vol I (stop bar interlock requirements), FAA AC 150/5340-30
Diagram: Stop Bar Circuit & Interlock Layout Drawing
Case Study: Division 24 — Complete Runway Lighting Failure
Symptom — A command issued from the ATC tower or ALCMS workstation to select the stop bar ON or OFF fails to reach or be executed by the field control system.
Remote command link between the ATC tower/ALCMS workstation and the stop bar's local control system — the communication network (serial/Ethernet/SCADA), protocol converters, and the field RTU/controller receiving the command.
Issue a series of test commands from ALCMS and confirm each is correctly received, executed, and acknowledged with accurate status feedback.
SOP: SOP-SPB-07 (Remote Command Link Test Procedure)
Standards: ICAO Annex 14 Vol I, ALCMS/SCADA vendor documentation
Diagram: ALCMS Network Architecture Drawing
Case Study: Division 01 — CCR Troubleshooting
Symptom — A circuit-level fault affects the full stop bar series loop, taking out the entire bar or a large section of it, distinct from an isolated fixture-level fault.
Stop bar series circuit — the CCR-fed series loop supplying the full stop bar fixture set, including the primary cable route and all in-line isolation transformers.
After repair, megger the full circuit end-to-end, re-energise, and confirm every fixture illuminates correctly and the interlock function still operates correctly.
SOP: SOP-SPB-01 (Stop Bar Fault Isolation Procedure), SOP-CCR-04 (CCR LOTO Procedure)
Standards: IEC 60364 (insulation testing), ICAO Annex 14 Vol I, FAA AC 150/5340-30
Diagram: Stop Bar Circuit & Interlock Layout Drawing
Case Study: Division 01 — CCR Troubleshooting; Division 25 — Field Case Study Troubleshooting
Symptom — An L-823 connector at a stop bar fixture position is found faulted, contributing to an outage, intermittent fault, or a failed insulation reading at that position.
L-823 connectors and base cans at individual stop bar fixture positions.
Re-energise and confirm the fixture illuminates correctly at all commanded states, and re-check the connector after a subsequent maintenance interval.
SOP: SOP-SPB-08 (Connector and Transformer Inspection Procedure)
Standards: FAA AC 150/5345-46, ICAO Annex 14 Vol I
Diagram: Stop Bar Base-Can Detail Drawing
Case Study: Division 25 — Field Case Study Troubleshooting
Symptom — An individual isolation transformer feeding a stop bar fixture is found faulted during investigation of an outage, dim output, or a failed insulation reading.
Individual isolation transformers feeding stop bar fixtures off the series circuit.
Re-energise and confirm the fixture illuminates correctly at the commanded intensity step, and re-megger the replacement transformer as a baseline reading.
SOP: SOP-SPB-08 (Connector and Transformer Inspection Procedure)
Standards: FAA AC 150/5345-26 (isolating transformers), ICAO Annex 14 Vol I
Diagram: Stop Bar Base-Can Detail Drawing
Case Study: Division 25 — Field Case Study Troubleshooting
Symptom — A Runway Guard Light (RGL) fixture, or a pair/row of fixtures, fails to illuminate or flash when the installation is energised.
Runway Guard Lights (RGL) — elevated Configuration A paired yellow flashing fixtures or in-pavement Configuration B row of yellow flashing fixtures, installed at the taxiway holding position to alert of proximity to the runway, fed via a dedicated series or parallel circuit and flash controller.
Re-energise and confirm both fixtures (or the full row) flash correctly in the specified alternating or sequential pattern before closing out.
SOP: SOP-GRD-01 (Runway Guard Light Fault Isolation Procedure)
Standards: ICAO Annex 14 Vol I (runway guard lights), FAA AC 150/5340-30, FAA AC 150/5345-46 (L-804)
Diagram: RGL Circuit and Flash Pattern Drawing
Case Study: Division 24 — Complete Runway Lighting Failure
Symptom — A Runway Guard Light fixture displays a colour other than yellow/amber, creating a discrepancy in the runway-proximity warning it is intended to provide.
RGL fixture lens/filter assembly and lamp/LED colour source.
Re-check chromaticity after correction and confirm visually against the paired/adjacent RGL fixture at night.
SOP: SOP-GRD-02 (Colour Verification Procedure)
Standards: ICAO Annex 14 Vol I, FAA AC 150/5345-46
Diagram: RGL Circuit and Flash Pattern Drawing
Case Study: Division 26 — Photometric & Intensity Compliance
Symptom — A Runway Guard Light fixture or its flash pattern comes and goes intermittently rather than holding a consistent, correctly timed flash.
RGL fixture, connector, transformer/ballast, and the flash controller output feeding that fixture.
Monitor the repaired fixture over several flash cycles and operating conditions before closing out.
SOP: SOP-GRD-01 (Runway Guard Light Fault Isolation Procedure)
Standards: ICAO Annex 14 Vol I, FAA AC 150/5345-46
Diagram: RGL Circuit and Flash Pattern Drawing
Case Study: Division 01 — CCR Troubleshooting
Symptom — The Runway Guard Light flash controller/synchroniser fails to produce the correct flash pattern — showing no flash, a steady state, or an incorrect rate/sequence.
RGL flash controller/synchroniser — the device generating and timing the alternating (Configuration A) or sequential (Configuration B) flash pattern for the runway guard lights, and any interface to ALCMS for status/command.
Confirm the corrected flash pattern matches the specification at the correct rate and synchronisation, observed directly at the fixture during a night check.
SOP: SOP-GRD-03 (Flash Controller Test Procedure)
Standards: ICAO Annex 14 Vol I, FAA AC 150/5340-30
Diagram: RGL Circuit and Flash Pattern Drawing
Case Study: Division 01 — CCR Troubleshooting
Quick answers about Stop Bar (SPB) / Runway Guard Light (GRD) troubleshooting in the AGL Troubleshooting Atlas.
Division 09 is the Stop Bar (SPB) / Runway Guard Light (GRD) Troubleshooting reference. It publishes 15 diagnostic topics, SPB-256 to GRD-270, across 2 subsections: Stop Bar Faults (11); Guard Light Faults (4).
Every topic follows the same diagnostic record: the symptom, equipment/system, possible causes ranked by likelihood (high, medium or low), required tools, safety precautions, diagnostic procedure, test points, root cause verification, corrective action, preventive action and related references (SOPs, standards, diagrams and case studies).
SPB-256 to SPB-266 (11 topics): Stop Bar Not Illuminated; Stop Bar Partially Illuminated; Stop Bar Flickering; Stop Bar Wrong Color; Stop Bar Intensity Failure; Stop Bar Control Failure; Stop Bar Interlock Failure; Stop Bar Remote Command Failure; Stop Bar Circuit Failure; Stop Bar Connector Failure; Stop Bar Transformer Failure.
GRD-267 to GRD-270 (4 topics): Guard Light Failure; Guard Light Wrong Color; Guard Light Intermittent; Guard Light Control Failure.
Each procedure starts with observation before any intervention. For example, SPB-256 (Stop Bar Not Illuminated) begins: Compare the ALCMS commanded state against the actual field state observed at the fixtures.
Each topic lists its own precautions. For example, SPB-256 (Stop Bar Not Illuminated) starts with: Coordinate airside access with ATC given the stop bar's location at an active holding position.
Related references in the topics include SOP-SPB-01 (Stop Bar Fault Isolation Procedure), SOP-CCR-04 (CCR LOTO Procedure), SOP-SPB-03 (Interlock Function Test Procedure), SOP-SPB-04 (Colour Verification Procedure), SOP-SPB-05 (Photometric Compliance Survey Procedure), SOP-SPB-06 (Stop Bar Control System Test Procedure), SOP-SPB-07 (Remote Command Link Test Procedure) and SOP-SPB-08 (Connector and Transformer Inspection Procedure), and 3 more.
Where a standard applies, it appears in the topic's Related References. Those cited in this division include ICAO Annex 14 Vol I, FAA AC 150/5340-30, FAA AC 150/5345-46, ICAO Annex 14 Vol I Appendix 2, IEC 60364 and FAA AC 150/5345-26.
Use the search box at the top of the page to filter the 15 published topics by code, fault name or keyword; matching topics open automatically. Each diagnostic record can also be downloaded as a Word (.doc) file.
A faulted stop bar or runway guard light is a safety-critical failure, not a routine maintenance item.
Build the technical knowledge to understand wig-wag and selective-switching behavior, interlock logic with ALCMS, and how to troubleshoot these systems with the urgency their safety function demands.