Category 02 · Insulation Resistance & Diagnostic Interpretation

AGL-CS-019 — Very High vs Low IR Test Result Investigation

The AGL Knowledge Hub | Engineering Case Study Series. A diagnostic-interpretation case where two circuits produced dramatically different IR readings while both remained operational — from test verification through trend analysis to condition-based decision-making.

Case ID

AGL-CS-019

Category

Insulation Resistance & Diagnostic Interpretation

Level

Expert

Case Type

Engineering Simulation

Primary Skill

Correct interpretation of insulation resistance test results

Important: This is an engineering simulation created for training. It is not presented as an actual airport incident. All readings, values, dates and outcomes are illustrative, and no airport, organisation, person or manufacturer is identified or implied.

1Case Study Overview

During a preventive maintenance program, two runway edge lighting circuits were tested using a 5 kV insulation resistance tester.

Circuit A produced an insulation resistance reading of greater than 1000 MΩ, while Circuit B produced a reading of 6 MΩ.

Surprisingly, both circuits were operating normally, and neither CCR reported an operational fault.

The maintenance team debated whether the very high reading indicated a perfect circuit and whether the low reading automatically required immediate cable replacement.

A detailed investigation revealed that IR values must always be interpreted together with historical trends, environmental conditions, circuit configuration, and sectional testing results.

This case demonstrates that the interpretation of an IR reading is often more important than the reading itself.

2Learning Objectives

After completing this case study, the learner should be able to:

  • Correctly interpret very high and low insulation resistance readings.
  • Understand the limitations of a single IR measurement.
  • Use historical IR trends for condition assessment.
  • Differentiate healthy insulation from misleading measurements.
  • Apply sectional IR testing.
  • Evaluate transformer and cable insulation separately.
  • Develop condition-based maintenance decisions.

3System Background

Insulation resistance testing evaluates the integrity of:

  • Underground primary cables.
  • Cable joints.
  • Connectors.
  • Isolating transformers.
  • Associated insulation systems.

The test measures leakage current through insulation.

A simplified relationship is:

Higher insulation resistance → Lower leakage current → Better insulation condition
Lower insulation resistance → Higher leakage current → Potential insulation deterioration

However, context is essential.

4Problem Statement

The reported condition was:

  • Circuit A: Greater than 1000 MΩ.
  • Circuit B: 6 MΩ.
  • Both circuits operational.
  • CCR healthy.
  • No visible cable damage.
  • Testing performed during dry weather.
Engineering Question

Which circuit presents the greater reliability risk, and how should each IR result be interpreted?

5Initial Observations

Parameter Circuit A Circuit B
CCR status Healthy Healthy
Circuit operation Normal Normal
IR result Greater than 1000 MΩ 6 MΩ
Historical IR Greater than 1000 MΩ 450 MΩ six months earlier
Weather Dry Dry

The historical data immediately became the most important factor.

6Initial Engineering Hypotheses

The maintenance team considered:

Hypothesis A

Circuit A is perfect.

Hypothesis B

Circuit B requires immediate replacement.

Hypothesis C

Circuit B has progressive insulation deterioration.

Hypothesis D

Circuit A may require additional verification.

Hypothesis E

Trend analysis is required before conclusions.

7Understanding IR Interpretation

A useful engineering interpretation is:

Greater than 1000 MΩ Generally healthy insulation
200–1000 MΩ Acceptable with trend monitoring
50–200 MΩ Early deterioration possible
10–50 MΩ Significant deterioration
Less than 10 MΩ Serious insulation degradation

However, the rate of change is often more important than the absolute value.

8Test Equipment

The investigation used:

  • 5 kV insulation resistance tester.
  • True-RMS multimeter.
  • Approved AGL circuit test equipment.
  • Transformer isolation equipment.
  • Circuit drawings.
  • Historical maintenance records.
  • Airport-approved PPE.

9Investigation

Step 1: Verify Test Procedure

Both circuits were tested under identical conditions. The measurements were confirmed as valid.

Step 2: Review Historical Trends

Circuit A

12 months earlier Greater than 1000 MΩ
6 months earlier Greater than 1000 MΩ
Current Greater than 1000 MΩ

Circuit A showed stable insulation behavior.

Circuit B

12 months earlier Greater than 1000 MΩ
6 months earlier 450 MΩ
3 months earlier 120 MΩ
Current 6 MΩ

Circuit B showed rapid deterioration.

Step 3: Sectional Isolation Testing

Circuit B was divided into sections.

Results:

CCR–S1 Greater than 500 MΩ
S1–S2 8 MΩ
S2–S3 Greater than 500 MΩ

The deterioration was localized.

Step 4: Transformer Isolation

Transformers in the affected section were disconnected. The IR remained low. This indicated that the primary cable section was the dominant source of insulation deterioration.

Step 5: Cable Investigation

Excavation found:

  • Moisture contamination.
  • Damaged cable sheath.
  • Insulation discoloration.
  • Early electrical tracking.

Circuit B had progressive underground cable deterioration.

10Root Cause

Training-Case Finding

Circuit A represented a stable healthy insulation system.

Circuit B represented progressive moisture-assisted cable insulation deterioration.

The low IR reading was important not because it was low, but because it had fallen dramatically over time.

11Corrective Action

Circuit A

  • No replacement required.
  • Continue routine monitoring.
  • Maintain historical trend records.

Circuit B

  1. Isolate affected section.
  2. Replace deteriorated cable.
  3. Install new approved cable joints.
  4. Improve drainage.
  5. Perform post-repair IR testing.
  6. Resume trend monitoring.

12Post-Repair Verification

Item Circuit A Circuit B
CCR operation Normal Normal
Circuit continuity Normal Normal
Insulation resistance Greater than 1000 MΩ Greater than 1000 MΩ
Maintenance documentation Updated Updated

Circuit B returned to healthy insulation values after cable replacement.

13Root-Cause Analysis

Problem

Low IR detected.

Test verified

Valid measurement.

Historical trend reviewed

Rapid deterioration identified.

Sectional testing

Fault section localized.

Cable excavated

Moisture damage confirmed.

Root Cause

Progressive cable insulation deterioration.

Corrective Action

Replace affected cable section.

14Why This Case Was Important

A common maintenance mistake is making decisions based only on the latest IR reading.

Correct engineering practice considers:

  • Historical trend.
  • Rate of deterioration.
  • Environmental conditions.
  • Circuit configuration.
  • Sectional localization.
  • Associated electrical symptoms.

A stable 100 MΩ circuit may be healthier than a rapidly declining 300 MΩ circuit.

15Engineering Lessons

01

A single IR reading should never be interpreted in isolation.

A single IR reading should never be interpreted in isolation.

02

Trend analysis is the most powerful insulation diagnostic tool.

Trend analysis is the most powerful insulation diagnostic tool.

03

Rapid deterioration is often more significant than the absolute value.

Rapid deterioration is often more significant than the absolute value.

04

Sectional testing should always follow abnormal IR results.

Sectional testing should always follow abnormal IR results.

05

Condition-based decisions require both measurement and history.

Condition-based maintenance decisions require both measurement and history.

16Engineer's Decision Point

You observe: Circuit A: Greater than 1000 MΩ. Circuit B: 25 MΩ. Circuit B was 400 MΩ three months earlier. What should you do?

A. Ignore both results.
B. Replace both circuits.
C. Investigate Circuit B immediately using sectional insulation testing.
D. Increase CCR current.
Correct answer: C. The rapid decline in Circuit B's IR is the critical diagnostic factor. Sectional testing will localize the deterioration for targeted repair.

17Knowledge Check

Q1. What was the most important diagnostic factor?
Answer: The insulation resistance trend.
Q2. Was Circuit B operational despite low IR?
Answer: Yes.
Q3. What caused Circuit B's deterioration?
Answer: Moisture-assisted cable insulation degradation.
Q4. Why was Circuit A not considered defective?
Answer: Its insulation remained stable over time.
Q5. What testing localized the fault?
Answer: Sectional insulation resistance testing.

18Interview Questions

Why is trend analysis more important than a single IR reading?
Can a circuit operate normally with low insulation resistance?
What causes progressive IR deterioration?
How would you localize a low IR fault?
What is the difference between a stable low IR value and a rapidly declining IR value?
Why should transformers be isolated during IR testing?
What environmental factors affect IR measurements?
When should a cable be replaced based on IR results?
How would you establish an IR monitoring program?
What documentation is essential for transformer and cable IR trending?

19Frequently Asked Questions

Quick answers about interpreting very high and low insulation resistance results, based on this case study.

Q1What is AGL-CS-019?

AGL-CS-019 is an engineering training case study on interpreting very high versus low insulation resistance readings from two operational runway edge lighting circuits. It is an engineering simulation created for training, not a report of an actual airport incident.

Q2What were the two IR results?

Both circuits were tested with a 5 kV insulation resistance tester. Circuit A read greater than 1000 MΩ and Circuit B read 6 MΩ, yet both circuits were operating normally and neither CCR reported a fault.

Q3Does a very high IR reading mean a circuit is perfect?

Not automatically. Circuit A represented a stable, healthy insulation system that needed no replacement, only routine monitoring and trend records, but a reading always needs context.

Q4Does a low IR reading always require immediate replacement?

No. Circuit B was important not because the reading was low, but because it had fallen dramatically over time. IR values must be interpreted together with historical trends, environmental conditions, circuit configuration and sectional testing.

Q5Why should a single IR reading not be read in isolation?

A single IR reading should never be interpreted in isolation. A trend of rapid decline is the critical diagnostic factor and shows deterioration that one snapshot cannot.

Q6What was done for each circuit?

Circuit A required no replacement, with routine monitoring and trend records continuing. For Circuit B the team isolated the affected section, replaced the deteriorated cable, installed new approved joints, improved drainage, tested post-repair IR and resumed trend monitoring.

Q7What was the root cause for Circuit B?

Progressive moisture-assisted cable insulation deterioration. After cable replacement, Circuit B returned to greater than 1000 MΩ.

Q8What should you do if Circuit B reads 25 MΩ after being 400 MΩ three months earlier?

Investigate Circuit B immediately using sectional insulation testing. The rapid decline is the critical diagnostic factor, and ignoring or replacing both circuits is not the right response.

Engineering & Expert Notes

Compare Circuits Like With Like

Interpretation

Length, age and temperature affect insulation values. Compare against similar circuits or the same circuit's history.

Look at the Rate of Change

Trending

A rapid fall is more concerning than a stable low value. Plot readings over time.

Test in Sections After an Abnormal Result

Follow-Up

Isolate the portion responsible before making repair decisions.

Keep Raw Readings and Method Notes

Records

Test voltage, duration and conditions are part of the result. Without them readings cannot be compared.

20Case Study Conclusion

Key Engineering Principle

The value of an insulation resistance test lies not only in the numerical reading but in its trend, location, and relationship to the operating condition of the AGL circuit.

Systematic historical analysis, sectional testing, transformer isolation, and cable investigation provide a far more accurate assessment of insulation health than a single measurement alone.

In AGL engineering, the trend of insulation resistance is often the most reliable predictor of future circuit failure.

Go Deeper

Turn Case Studies Into Engineering Capability

A case study shows you how a problem is investigated. Precision AGL Academy helps you build the knowledge to understand why it happens, diagnose it systematically, and apply the right engineering approach.