Aviation Red Obstacle Light for Aircraft Obstruction Marking
A dedicated red signal that identifies structures aircraft must avoid
Aviation red obstacle lights identify structures that require aviation marking and provide visual indication during the applicable operating period. They are used on buildings, towers, masts, cranes and other structures that may present an obstacle to aircraft. Precision AGL Solutions supplies them for new installations, replacement projects and upgrades, selected by required intensity, operating mode, structure characteristics, mounting arrangement, electrical supply and applicable aviation authority requirements.
Aviation Red Obstacle Light
The light provides a dedicated red visual signal for structures requiring obstruction marking. It may be installed as an individual unit or as part of a larger system with multiple lights and lighting levels, and may be steady-burning or flashing depending on the approved configuration. Selection can be based on:
- Required luminous intensity
- Red-light characteristics
- Steady or flashing operation
- Mounting location
- Electrical supply
- Control requirements
- Monitoring requirements
- Environmental conditions
For structures needing multiple obstruction-lighting levels, the lights can be incorporated into a coordinated system where required.
Where Aviation Red Obstacle Lights Are Used
The final arrangement should follow the approved aviation obstruction-lighting assessment and applicable project requirements.
Intensity Selection and Steady or Flashing Operation
Light Intensity Selection
- Structure height and location
- Surrounding airspace
- Day/night operating conditions
- Required visual conspicuity
- Applicable obstruction-light classification
- Existing lighting arrangement
- Select as part of the complete obstruction-lighting design, not by physical dimensions alone
Steady or Flashing Operation
- Obstruction-light classification
- Structure type
- Aviation authority requirements
- Day/night operation
- Coordination with other obstruction lights
- Existing control system
- Where flashing is required, confirm flash characteristics during product selection
What the Light Provides
- Aviation red obstruction lighting
- Suitable for buildings, towers, masts and cranes
- Steady or flashing configurations
- LED-based configurations where applicable
- Defined optical output
- Compact structure-mounted design
- Outdoor-rated construction
- Project-specific mounting options
- Electrical configurations for different site supplies
- Optional control and monitoring interfaces
- Suitable for new and replacement installations
Typical Specification
| Parameter | Typical Specification |
|---|---|
| Light Type | Aviation red obstacle light |
| Light Source | LED or approved source, configuration dependent |
| Colour | Aviation-specified red |
| Intensity | Project and classification dependent |
| Operation | Steady or flashing |
| Flash Characteristics | Configuration dependent |
| Power Supply | Model dependent |
| Power Consumption | Model dependent |
| Mounting | Structure, mast, pole, crane or project-specific |
| Dimensions | Model dependent |
| Cable / Connection | Project-specific |
| Monitoring | Optional, where specified |
| Environmental Protection | Outdoor-rated construction, configuration dependent |
| Operating Temperature | Model dependent |
Exact luminous intensity, electrical characteristics, dimensions and environmental ratings should be confirmed against the selected product configuration.
Optical Characteristics
The optical system provides visible red output from the required viewing directions. Selection may consider:
- Luminous intensity
- Red colour characteristics
- Horizontal coverage
- Vertical distribution
- Steady or flashing output
- Visibility under applicable operating conditions
For multi-level structures, consider each light's optical characteristics together with the position and geometry of the structure.
Mounting Arrangements
Typical mounting locations:
- Tower tops
- Mast platforms
- Building rooftops
- Structural steelwork
- Crane structures
- Pole assemblies
- Equipment platforms
- Dedicated obstruction-light brackets
The mounting should maintain the required optical orientation and give secure mechanical support under expected site conditions. Project-specific brackets or adapters can be considered.
Electrical Configuration, Automatic Control and Monitoring
Electrical Configuration
- Supply voltage
- AC/DC operation
- Power consumption
- Circuit protection and surge protection
- Cable entry and connector arrangement
- Earthing
- Local control and remote monitoring
Automatic Control
- Day/night switching
- Photocell operation
- Flash control
- System enable/disable
- Fault indication
- Remote status monitoring
- Coordinated operating state across multiple levels
Monitoring & Fault Indication
- Light status
- Power status
- Controller status
- Flashing status
- Communication status
- Fault indication
- Remote alarm output
Coordinate the electrical interface with the overall obstruction-lighting system. Monitoring can be coordinated with site SCADA, building-management or airport infrastructure where compatible.
Installation Considerations
Before installation, confirm:
- Approved obstruction-lighting layout
- Required intensity
- Light positions
- Required mounting elevation
- Optical orientation
- Structure geometry
- Electrical supply
- Control and monitoring requirements
- Cable routing
- Surge and lightning protection
- Maintenance access
Install according to the approved project drawings and applicable aviation requirements.
Environmental Performance
Obstacle lights are intended for outdoor operation and may be exposed to rain and moisture, dust, solar radiation, temperature variation, wind, vibration, coastal exposure and industrial contamination.
The enclosure, optical window, cable entries and mounting materials should suit the site conditions. For corrosive or severe environments, consider appropriate material and protective-finish selection.
Commissioning
Commissioning should verify that the installed light operates according to the approved configuration:
- Inspect the mounting arrangement.
- Verify optical orientation.
- Check electrical connections.
- Confirm supply voltage.
- Test steady or flashing operation.
- Verify red light output.
- Test control functions.
- Check monitoring and alarm interfaces.
- Inspect cable entries and environmental sealing.
- Record commissioning results.
Where required, perform photometric verification using suitable calibrated equipment.
Maintenance and Troubleshooting
Routine maintenance includes visual inspection, cleaning the optical surface, checking mounting hardware, cable entries and electrical connections, functional testing, verifying control operation and monitoring signals, inspecting enclosure integrity and replacing damaged components. Intervals should be based on the installation environment, manufacturer recommendations and site procedures.
| Condition | Possible Cause | Recommended Check |
|---|---|---|
| Light not operating | Power or control fault | Check supply, protection and controller |
| Reduced visibility | Dirty or damaged optical surface | Inspect and clean the lens |
| Incorrect flashing | Control/configuration issue | Verify flash settings |
| Intermittent operation | Supply or connection problem | Inspect cables and terminals |
| Monitoring alarm | Light or communication fault | Check system status |
| Moisture inside enclosure | Seal or cable-entry issue | Inspect enclosure and sealing |
| Light movement | Loose mounting | Inspect and secure mounting hardware |
Replacement and Retrofit
Aviation red obstacle lights can replace older or obsolete obstruction-lighting equipment. Retrofit selection should consider:
- Existing light classification
- Existing mounting location
- Required intensity
- Operating mode
- Supply voltage
- Control system
- Monitoring interface
- Cable arrangement
- Structure geometry
- Current aviation requirements
A replacement should maintain the required optical and operational characteristics of the approved obstruction-lighting arrangement.
Ordering Checklist
For product selection, provide where available:
- Structure type, height and location
- Applicable aviation authority
- Required obstruction-light classification
- Required intensity
- Red-light requirement
- Steady or flashing operation
- Quantity of lights
- Mounting arrangement
- Available power supply
- Existing control system
- Monitoring requirements
- Environmental conditions
- New installation or replacement status
Red Mode and Intensity Follow the Light Type
| Light type | Mode and colour | Typical use |
|---|---|---|
| Low-intensity (ICAO Types A and B; FAA L-810) | Steady red (about 10 cd Type A, 32 cd Type B and L-810) | Lower levels of a structure, and low obstacles |
| Medium-intensity, ICAO Type B / FAA L-864 | Flashing red (about 2,000 cd) | Night marking; the red night element of a dual system |
| Medium-intensity, ICAO Type C | Steady red (about 2,000 cd) | Night marking of extensive objects |
Points to Check
- A red light alone does not mark a tall structure by day: taller structures normally need flashing white lights for day and twilight, with red used at night
- Provide enough lights per level so at least one is visible from every direction
- Flashing lights on one structure should flash simultaneously, so a controller or synchronisation is needed across levels
- FAA changed its LED red obstruction-light specification so lights are visible to certain night-vision-goggle systems, so confirm the unit is certified to the current AC 150/5345-43J
- Servicing a tower- or mast-mounted light is work at height on a live supply: isolate and lock out the supply, work under a permit-to-work and use approved fall protection
- A failed light needs to be repaired promptly and the authority notified of the outage as its rules require
Engineering Note
Intensity, number of levels and spacing come from the approved obstruction-lighting assessment. Medium and high-intensity values differ between ICAO and FAA, so confirm the standard used for the project.
Standards, References and Documents
Standards and References
- ICAO Annex 14 Vol. I, Chapter 6 (obstacle lighting) and Doc 9157 Aerodrome Design Manual, Part 4
- FAA AC 70/7460-1 (obstruction marking and lighting; edition 1N issued 11 Aug 2026, cancelling 1M) with AC 150/5345-43J (obstruction lighting equipment)
- DGCA India CAR Section 4 and aviation authority NOC conditions
- Requirements vary by structure type, location, classification and aviation authority
- Review the product and installation against the applicable aviation obstruction-lighting requirements
- Review against approved project documentation and current authority criteria
- Confirm any specific national aviation regulation, airport standard or engineering specification during final selection
Documentation
- Product datasheet
- Photometric information
- Electrical specifications
- Mounting drawings
- Installation instructions
- Control and monitoring information
- Wiring diagrams
- Maintenance recommendations
- Compliance documentation, where applicable
Aviation Lighting for Obstacle Applications
Precision AGL Solutions supplies aviation lighting equipment for airport, airfield, infrastructure and aviation-obstacle applications.
Aviation Red Obstacle Light — Frequently Asked Questions
What is an aviation red obstacle light?
It is a light that provides a dedicated red visual signal for structures requiring obstruction marking. It may be installed as an individual unit or as part of a larger system with multiple lights and lighting levels, and may be steady-burning or flashing depending on the approved configuration.
Where are aviation red obstacle lights used?
Typical uses are buildings and rooftop structures, communication towers and telecommunications masts, utility and transmission structures, tall poles and elevated equipment, construction and mobile cranes, industrial installations and airport-adjacent structures, temporary or permanent obstacles, and replacement of existing obstruction lights. The final arrangement should follow the approved aviation obstruction-lighting assessment.
What light types and intensities are used?
Low-intensity lights (ICAO Types A and B; FAA L-810) are steady red, about 10 cd for Type A and 32 cd for Type B and L-810, for the lower levels of a structure and low obstacles. Medium-intensity ICAO Type B / FAA L-864 lights are flashing red at about 2,000 cd for night marking, and ICAO Type C is steady red at about 2,000 cd for night marking of extensive objects. Intensity, number of levels and spacing come from the approved obstruction-lighting assessment, and medium and high-intensity values differ between ICAO and FAA, so confirm the standard used for the project.
Is a red light alone enough to mark a tall structure?
No. A red light alone does not mark a tall structure by day: taller structures normally need flashing white lights for day and twilight, with red used at night. Provide enough lights per level so that at least one is visible from every direction.
Should the light be steady or flashing?
The choice depends on the obstruction-light classification, structure type, aviation authority requirements, day and night operation, coordination with other obstruction lights and the existing control system. Where flashing is required, confirm the flash characteristics during product selection. Flashing lights on one structure should flash simultaneously, so a controller or synchronisation is needed across levels.
How are aviation red obstacle lights mounted?
Typical mounting locations are tower tops, mast platforms, building rooftops, structural steelwork, crane structures, pole assemblies, equipment platforms and dedicated obstruction-light brackets. The mounting should maintain the required optical orientation and give secure mechanical support under the expected site conditions, and project-specific brackets or adapters can be considered.
What control and monitoring options are available?
Automatic control can include day/night switching, photocell operation, flash control, system enable and disable, fault indication, remote status monitoring and a coordinated operating state across multiple levels. Monitoring can cover light, power, controller, flashing and communication status, fault indication and remote alarm output, and can be coordinated with site SCADA, building-management or airport infrastructure where compatible.
What should be confirmed before installation, and what is checked at commissioning?
Before installation confirm the approved obstruction-lighting layout, required intensity, light positions and mounting elevation, optical orientation, structure geometry, electrical supply, control and monitoring requirements, cable routing, surge and lightning protection, and maintenance access. Commissioning checks the mounting, optical orientation, electrical connections, supply voltage, steady or flashing operation, red light output, control functions, monitoring and alarm interfaces, and cable entries and sealing, and the results are recorded. Where required, perform photometric verification using suitable calibrated equipment.
How should an obstacle light be maintained safely?
Routine maintenance includes visual inspection, cleaning the optical surface, checking mounting hardware, cable entries and electrical connections, functional testing, verifying control operation and monitoring signals, and inspecting enclosure integrity. Servicing a tower- or mast-mounted light is work at height on a live supply, so isolate and lock out the supply, work under a permit-to-work and use approved fall protection. Intervals should be based on the installation environment, manufacturer recommendations and site procedures.
What are common faults, and what happens if a light fails?
Typical conditions are a light not operating (check supply, protection and controller), reduced visibility (inspect and clean the lens), incorrect flashing (verify flash settings), intermittent operation (inspect cables and terminals), monitoring alarms, moisture inside the enclosure and light movement from loose mounting. A failed light needs to be repaired promptly and the authority notified of the outage as its rules require.
Can an aviation red obstacle light replace an older obstruction light?
Yes. These lights can replace older or obsolete obstruction-lighting equipment. Retrofit selection should consider the existing light classification, mounting location, required intensity, operating mode, supply voltage, control system, monitoring interface, cable arrangement, structure geometry and current aviation requirements, and the replacement should maintain the required optical and operational characteristics of the approved arrangement.
Which standards apply to aviation red obstacle lights?
References include ICAO Annex 14 Vol. I Chapter 6 (obstacle lighting) with Doc 9157 Part 4, FAA AC 70/7460-1 (obstruction marking and lighting) with AC 150/5345-43J (obstruction lighting equipment), and DGCA India CAR Section 4 with aviation authority NOC conditions. FAA changed its LED red obstruction-light specification so lights are visible to certain night-vision-goggle systems, so confirm the unit is certified to the current AC 150/5345-43J.
What information is needed to select an obstacle light?
Provide the structure type, height and location, the applicable aviation authority, the required obstruction-light classification and intensity, the red-light requirement, steady or flashing operation, quantity of lights, mounting arrangement, available power supply, existing control system, monitoring requirements, environmental conditions, and whether it is a new installation or a replacement.
Procurement Information for Indian Projects
Indian public tenders commonly ask for the documents below. State which ones your tender requires when you send the enquiry, so they are covered in the quotation.
- Manufacturer / OEM authorisation
- Country of origin and local-content declaration (for Make in India purchase preference)
- Type-test and routine-test certificates, and the FAA / ICAO / IEC compliance documents named in the specification
- Datasheets, drawings and installation instructions
- Warranty, delivery period and spares support
- GeM catalogue or tender-portal requirements, where applicable
Request Obstacle-Light Product Selection
Planning aviation obstruction lighting for a building, tower, mast, crane or other potential aviation obstacle? Send the structure type, height, location, required intensity, operating mode, mounting arrangement, power supply and applicable project specification. We can recommend the appropriate Aviation Red Obstacle Light configuration, including optical characteristics, mounting, electrical interface and control options.
Engineering Note
The required intensity, colour characteristics, steady/flashing operation, mounting arrangement and control requirements are application- and authority-dependent. Exact product parameters should be confirmed against the approved aviation obstruction-lighting assessment and current requirements applicable to the project before procurement or installation.
Product Disclaimer
Product availability, configuration, dimensions, electrical characteristics, photometric performance, certifications and compliance status depend on the selected manufacturer and project specification. The technical values published on this page should not be treated as a substitute for the manufacturer's current approved Technical Data Sheet.
Final selection shall be based on the approved project specification, applicable aviation standards, authority requirements, manufacturer documentation and site conditions. Use of this page is also subject to the Legal Notice, Disclaimer & Terms of Use.
Standards and editions referenced on this site are listed on the Standards Reference page.