How is a connector selected?

Four decisions, taken in order, that narrow the choice to the right sealed connector or joint for a series circuit.

SELECTION FLOWCHART · FOUR DECISIONS IN ORDER 1SIDE Which side of the transformer? Primary, in the loop → Carries full loop current Secondary, to the fitting → Isolated, one fitting 2JOINT Plug-in or permanent? Must be unplugged → Sealed plug and receptacle Joins cable lengths → Sealed in-line joint 3FIT What must it match? Cable or lead → Conductor size and jacket Circuit rating → Voltage and current 4LOCATION Where will it sit? Base can or pit → Sealed against water Sign or housing → Fits and stays reachable CONFIRM BEFORE ORDERING type and keying · rating · cable fit · seal or kit · standard compliance FLOWCHART · THE MANUFACTURER DATA SHEET AND STANDARD DECIDE THE FINAL CHOICE
decision stage
option and result
final check
The Fact FAA AC 150/5345-26

Connectors are made on site and are the usual weak point of a circuit, so the right one matters. The side of the transformer sets the duty, since a primary connector carries the full loop current and a secondary connector serves one fitting. Whether it must be plugged and unplugged sets the type, it must match the cable and circuit rating, and the location decides how it is sealed.

The flowchart only narrows the choice. The final connector is confirmed against the design for type and keying, rating, cable fit and seal or kit, and against the standard it must meet.

SidePrimary or secondary
JointPlug-in or permanent
FitMatches cable and rating
LocationSealed for below ground
ReferenceFAA AC 150/5345-26 (L-823) · ICAO Doc 9157 Part 5
Simplified selection guide, not a design. Connector types, ratings and mating arrangements vary by manufacturer and come from the circuit design, the applicable standard and the data sheet. Isolate the CCR, lock out and prove the circuit dead before any connector is touched, and never separate a primary connector on an energised circuit.
Entry 16 · Cable selection Entry 18 · Sign selection

Frequently Asked Questions

Q1How is an AGL connector selected?

By working through a few decisions in order: which side of the isolating transformer it joins, whether the joint must be plugged and unplugged or made permanent, what cable and circuit rating it must match, and where it will sit. The result is then checked against the data sheet and standard.

Q2Why does it matter whether a connector is primary or secondary?

A primary connector is part of the series loop and carries the full circuit current, so a poor one can affect every light on the circuit. A secondary connector is on the isolated side and serves one fitting, so the usual effect is one dim or dark light. Each must be rated for its own side.

Q3When is a plug-in connector used and when a permanent joint?

A plug-in connector lets a transformer, fitting or sign be disconnected, tested or replaced without re-jointing the cable. A permanent in-line joint joins two lengths of cable where no disconnection is needed. The design and the manufacturer’s instructions decide which is used where.

Q4What must a connector match?

The cable or lead it is made onto, in conductor size, insulation and jacket, and the circuit it serves, in voltage and current rating, such as the 5 kV class of primary series cable or the lower-voltage class of secondary cable. It should also be keyed to mate one way and be compatible with the part it mates to, which the manufacturer confirms.

Q5What should be checked before the choice is final?

That the type, keying and rating match the design, that it fits the cable or lead, that the seal or kit suits the location, and that the connector meets the applicable standard. The manufacturer’s data sheet and the standard decide, and the finished joint is inspected and tested.

Precision AGL Academy

See It. Understand It. Then Learn How to Engineer It.

Recognising an AGL system visually is the first step. The next step is knowing how to design, install, test, commission and maintain them correctly.

Build Practical AGL Engineering Skills

Go deeper with structured training from Precision AGL Academy, covering:

AGL Fundamentals Design & Electrical Engineering Approach Lighting Photometry Installation & Commissioning Maintenance & Troubleshooting

Learn how each light, sign and circuit works as part of a complete airport lighting system, not just as an isolated diagram.

See. Understand. Apply. Engineer.