CCR internal architecture

What is inside the cabinet and how it is wired: input protection, power stage, transformer, sensing and control. Select a part to see its job and what to check, or switch layers to follow just the power, control, cooling or protection.

power wiring
sensing / control signals (dashed)
selected part
The Fact Construction

Inside a CCR the power path runs from the input isolator and contactor through the power stage to the output transformer and out to the series circuit. A separate sensing and control path measures the output current and tells the power stage what to do, while the protection parts, the cooling and the front panel support it.

Knowing the layout helps you inspect and test in the right order: what must be isolated, where heat builds up, where terminations carry the most current, and which signals the control board relies on.

Power pathIsolator, contactor, power stage, transformer, output terminals
Control pathOutput current sensor, control board, auxiliary supply, front panel
HeatPower stage and transformer; removed by heatsink and fan
ReferenceIEC 61822 · FAA AC 150/5345-10 · ICAO Doc 9157 Pt 5
Schematic — a typical layout for illustration. Real cabinets differ in arrangement, parts and wiring by manufacturer and model. Use the manufacturer’s drawings, and isolate and lock out before opening any cabinet.
Entry 1 · CCR system overview Entry 3 · CCR power input

Frequently Asked Questions

Q1What is inside a CCR cabinet?

Input protection and a contactor, a thyristor power stage on a heatsink, the output transformer, an output current sensor, a control board with an auxiliary supply, cooling, a front panel and the terminals.

Q2What is the power path inside a CCR?

Supply, input isolator and contactor, power stage, output transformer, then out through the output terminals to the series circuit.

Q3What is the control path?

The output current sensor measures what actually flows and feeds the control board, which sets the firing of the power stage to match the selected intensity step.

Q4Where does a CCR make the most heat?

In the power stage and the transformer. A heatsink and fan carry the heat away, so clean filters and clear air paths matter.

Q5Why does the layout matter for maintenance?

It shows what must be isolated, where terminations carry the most current, where heat builds up and which signals the control board relies on, so inspection and testing can be done in a safe, logical order.

Q6Do all CCRs look like this?

No. Layouts, parts and wiring vary by manufacturer and model. Use this as a general guide and the manufacturer's drawings for a specific unit.

Precision AGL Academy

See It. Understand It. Then Learn How to Engineer It.

Recognising an AGL system visually is the first step. The next step is knowing how to design, install, test, commission and maintain them correctly.

Build Practical AGL Engineering Skills

Go deeper with structured training from Precision AGL Academy, covering:

AGL Fundamentals Design & Electrical Engineering Approach Lighting Photometry Installation & Commissioning Maintenance & Troubleshooting

Learn how each light, sign and circuit works as part of a complete airport lighting system, not just as an isolated diagram.

See. Understand. Apply. Engineer.