What is CCR communication?

The two-way link that lets the airfield lighting control system switch and dim a constant current regulator and see its state, current and faults.

CCR LINKED TO CONTROL · WHAT CCR COMMUNICATION CARRIESALCMSPLC · SCADAtower / control roomCCRCONTROLLERcommunication portSTEP · CURRENTCOMMANDSSTATUS & ALARMSlinkLOCALCONTROL PANELTO SERIES CIRCUIT1CONTROL SOURCEALCMS, PLC or SCADA at tower or control room2COMMUNICATION LINKhardwired, serial, Ethernet or fibre3COMMANDSon / off, brightness step, local / remote4STATUS FEEDBACKstate, step, output current5ALARMS & FAULTSopen circuit, overcurrent, earth leakage6LINK FAILUREwatchdog, safe state, local fallback1 · Control source2 · Communication link3 · Commands4 · Status feedback5 · Alarms & faults6 · Link failure
commands / local control
communication link
alarms & faults
status feedback
link failure behaviour
The Fact System function

CCR communication connects each constant current regulator to the airfield lighting control and monitoring system. The control system sends commands, such as switch on or off and select a brightness step. The CCR returns status, including its state, selected step and output current, and raises alarms for faults such as open circuit, overcurrent or earth leakage.

The link may be hardwired control and status signals, a serial connection or an Ethernet network, often over fibre optic cable for long runs and better immunity to interference. The CCR can also be operated from its own local panel, and what it does if the link fails is set in its configuration, with a communication alarm raised at the control system.

  1. Command. The control system or the tower requests a circuit on, off or at a set brightness step.
  2. Transmit. The command travels over the hardwired, serial or network link to the CCR controller.
  3. Act. The controller checks local or remote mode and sets the output to the requested step.
  4. Report. The CCR sends back its state, step and output current.
  5. Alarm. Any fault is signalled to the control system and shown to staff.
  6. Supervise the link. A lost link raises an alarm and the CCR follows its configured fallback.
Purpose Let the control system operate and supervise a CCR remotely
Commands On / off, brightness step, local / remote mode
Feedback State, selected step, output current, fault and alarm status
Link types Hardwired signals, serial, Ethernet, fibre optic
Key protection Isolation and surge protection against interference and transients
Reference IEC 61822 · FAA AC 150/5345-10 · FAA AC 150/5345-56 · ICAO Doc 9157 Pt 5
Schematic — a generic CCR-to-control link drawn for clarity. Interfaces, protocols and failure behaviour differ by manufacturer and control system, so follow the CCR manual and the site’s control-system documentation.
Entry 20 · CCR remote control Entry 22 · CCR control architecture

Frequently Asked Questions

Q1What is CCR communication in airfield lighting?

The exchange of commands, status and alarms between a constant current regulator and the airfield lighting control and monitoring system, so a circuit can be switched, dimmed and supervised from a remote point.

Q2What does a CCR send and receive?

It receives commands such as on or off and brightness step, and it reports its state: on or off, selected step, output current and fault or alarm conditions such as open circuit, overcurrent or earth leakage.

Q3How does a CCR connect to the control system?

By hardwired control and status signals, by a serial link, or by an Ethernet network, often over fibre optic cable for long distances and better immunity to interference and surges. The method depends on the CCR model and the control system.

Q4What is local and remote control?

Local control operates the CCR from its own panel, normally for maintenance and testing. Remote control accepts commands from the control system. The CCR works from only one source at a time, and a local selection normally overrides remote commands.

Q5What happens if communication is lost?

The CCR behaviour is set at configuration: for example hold the last state, default to a safe step or switch to local operation. The control system raises a communication alarm so staff know the circuit is no longer supervised.

Q6Why is the link protected against interference and surges?

CCRs sit near high-voltage cables and lightning-exposed circuits. Fibre optic links, isolation and surge protection stop interference and transients from corrupting commands or damaging control equipment.

Precision AGL Academy

See It. Understand It. Then Learn How to Engineer It.

Recognising an AGL system visually is the first step. The next step is knowing how to design, install, test, commission and maintain them correctly.

Build Practical AGL Engineering Skills

Go deeper with structured training from Precision AGL Academy, covering:

AGL Fundamentals Design & Electrical Engineering Approach Lighting Photometry Installation & Commissioning Maintenance & Troubleshooting

Learn how each light, sign and circuit works as part of a complete airport lighting system, not just as an isolated diagram.

See. Understand. Apply. Engineer.