Calculator #21

Primary Cable Resistance

Loop resistance of a primary AGL cable from conductor size, length and temperature, with a field-test comparison.

About this calculator

Resistance is the starting point for every cable calculation in a series circuit. Enter each cable section, and the tool gives the resistance at 20 °C and at your operating temperature, shows how it moves with temperature, compares the other conductor sizes, and checks a measured reading against the expected value.

Quick start

Cable Sections

Rule note

A series circuit runs out to the last fixture and back, so the conductor length is the loop.

Section / descriptionConductorLength (m)Resistance (Ω)

Conditions

Rule note

Copper resistance rises about 0.393 % per °C above 20 °C. Use the expected conductor temperature.

Rule note

Used by any section set to "Custom". Take it from your cable data sheet.

Rule note

If entered, the comparison shows the longest loop each conductor can be for that resistance at your temperature. Leave 0 to skip.

Field Test Check (optional)

Rule note

Leave 0 to skip. The reading is corrected to 20 °C and compared with the calculated value.

Rule note

Your own acceptance rule.

FAQ

Primary Cable Resistance Calculator: Frequently Asked Questions

Quick answers on the loop resistance of a primary AGL cable and the field-test comparison.

What does the Primary Cable Resistance calculator do?

It calculates the loop resistance of a primary AGL cable from conductor size, length and temperature. It gives the resistance at 20 degrees C and at your operating temperature, shows how it moves with temperature, compares the other conductor sizes, and checks a measured reading against the expected value. Resistance is the starting point for every cable calculation in a series circuit.

Should I enter the loop length or the route length?

Either. A series circuit runs out to the last fixture and back, so the conductor length is the loop. You can enter the total loop length, or the one-way route length, which is doubled. Lengths can be in metres or feet, and you add one row per cable section. Each section's resistance at 20 degrees C is its resistance per km times its length divided by 1,000, and the sections are added.

How is temperature handled?

The resistance at temperature is the resistance at 20 degrees C times 1 plus 0.00393 times the temperature minus 20, which is the usual coefficient for copper, about 0.393 percent per degree C. A warm cable in summer or a buried cable in winter can differ noticeably from the 20 degrees C value, so use the expected conductor temperature.

What is the target loop resistance for?

If you enter a target loop resistance, the conductor comparison shows the longest loop each conductor size can be for that resistance at your temperature. The length is the target divided by the resistance per km at 20 degrees C times the temperature factor, divided by 1,000. Leave it at 0 to skip.

How does the field test check work?

The measured loop resistance is corrected to 20 degrees C using the temperature at the test, and compared with the calculated value as a percentage difference against your own tolerance. A reading well above expected can point to a poor joint or a longer route than assumed. A reading below expected can point to a larger conductor or a shorter route. Both need checking on site.

Can you give a worked example?

A #8 AWG loop of 3,000 m at 2.061 ohms per km has a resistance of 6.183 ohms at 20 degrees C. At 40 degrees C the temperature factor is 1.0786, which gives 6.669 ohms. A measured 6.35 ohms at 30 degrees C corresponds to 6.11 ohms at 20 degrees C, a difference of minus 1.2 percent from 6.183 ohms.

What does the tool not do?

It does not calculate voltage drop or loss (see Calculator #15), include connectors, splices or cable reactance, or cover aluminium conductors. Stranded conductors read slightly higher than the solid-wire figures.

Are the resistance values final?

No. They are nominal DC figures for copper, so confirm them against your cable data sheet. Final design shall be verified against the cable manufacturer's data and the applicable project specification.