Calculator #51

CCR Performance / Efficiency Calculator

Turn FAT and SAT meter readings into input and output kVA, power factor, efficiency, losses and a pass or fail summary.

About this calculator

A constant current regulator is judged on what it takes in, what it delivers and how steady the output current stays. Enter the readings from the power analyser and the output test, set the limits from your specification, and this tool works out the rest, including heat released into the CCR room and the current deviation at each load point and brightness step.

CCR & Input Readings

Nameplate rating, kW treated as kVA.
Line-to-line for a three-phase supply.
From the power analyser or wattmeter.

Output Readings

Across the load or the series circuit.
1.00 for a resistive load bank. For a real circuit, use the measured value.
Reference for the regulation checks.

Acceptance Limits from your specification

Placeholder. Use the specification or data sheet figure.
Placeholder. Use the specification or data sheet figure.
Placeholder, in amperes. FAA AC 150/5345-10 (edition F onward) allows ±0.1 A on a 6.6 A CCR and ±0.3 A on a 20 A CCR; confirm in the edition named in your specification. Applies to the load points and the steps below.

Load Regulation optional

Measured output current at different loads on the CCR. Clear a row to leave it out.

Load (% of rated)Output current (A)DeviationResult
——
——
——
——

Brightness-Step Currents optional

Choosing a set loads its nominal currents, the rated output current and the usual tolerance (±0.1 A for 6.6 A, ±0.3 A for 20 A). Edit them afterwards if your specification differs.
StepNominalMeasured (A)DeviationResult
B12.8 A——
B23.4 A——
B34.1 A——
B45.2 A——
B56.6 A——
FAQ

CCR Performance / Efficiency Calculator: Frequently Asked Questions

Quick answers on how the calculator works up CCR test readings for FAT and SAT.

What does the CCR Performance / Efficiency Calculator do?

It works up test readings from a constant current regulator for factory and site acceptance testing. From the input and output readings it calculates input and output kVA, power factor, efficiency, total loss, loading and load impedance. It also checks load regulation and brightness-step currents against limits you enter, and it produces a PDF test report.

How are CCR efficiency and loss calculated?

Output real power is output kVA times the load power factor, and efficiency is output real power divided by input real power. Loss is input real power minus output real power. The result depends on meter accuracy, waveform distortion and the load type, so record the instrument class with the test.

How is input power factor worked out?

Input apparent power is voltage times current divided by 1,000, multiplied by the square root of 3 on a three-phase supply. Power factor is the input real power from your power analyser or wattmeter divided by that apparent power. For a three-phase supply, enter the line-to-line voltage.

How does the load regulation and step current check work?

Each measured current is compared with its nominal value, and the result passes or fails against a tolerance in amperes, because the limit is an absolute current and not a percentage. FAA AC 150/5345-10 (edition F onward) allows plus or minus 0.1 A on a 6.6 A CCR and plus or minus 0.3 A on a 20 A CCR. Confirm this in the edition named in your specification. The regulation spread is the gap between the highest and lowest load-point current as a percentage of rated current.

Are the acceptance limits built in?

No. Minimum efficiency, minimum input power factor and output current tolerance are placeholders until you enter the figures from your specification or the CCR data sheet. Selecting a CCR class and step set loads the nominal step currents and the usual tolerance, which you can edit if your specification differs.

Can you give a worked example?

A 10 kW CCR fed at 230 V and 45 A single-phase draws 10.35 kVA and 9.85 kW, a power factor of 0.952. With 1,400 V at 6.6 A and a power factor of 1.00, the output is 9.24 kW. That gives an efficiency of 93.8 percent, a loss of 0.61 kW, which is about 2,081 BTU per hour of heat into the room at 3,412 BTU per kW, and a loading of 92.4 percent.

What does the calculator not cover?

It does not measure harmonics, ripple or waveform shape, and it assumes the readings are true RMS. A CCR's rated size, step currents and test conditions come from its data sheet and the applicable standard. The nameplate rating in kW is treated as kVA.

Can I use the result as the final acceptance decision?

No. It is an engineering reference tool. Acceptance shall be judged against the project specification and the CCR manufacturer's test procedure. The acceptance summary and PDF report record the checks and the limits you entered, so those limits must come from your own documents.