Calculator #66

AGL Fault Location Calculator (Advanced)

Classify the fault, calculate a distance by Murray loop, conductor resistance, TDR or capacitance, narrow it with a half-split tracker, and combine every estimate into one search window.

About this calculator

Start by classifying the fault from your IR, continuity and CCR readings. Then calculate a distance with one or more methods, narrow it down with the half-split tracker, and read the combined search window along the circuit. Several methods that agree give a narrow, confident window. Every distance is measured from the same end of the circuit.

Quick start

1 · Circuit data

Rule note

One-way route length of the cable under test.

Rule note

Used to name the nearest fixture and set the half-split resolution.

Rule note

Needed for the conductor resistance method (B).

2 · Classify the fault

Rule note

Placeholder. Use your specification.

Rule note

From the Circuit Voltage calculator or the as-built load.

3 · Distance methods

A · Murray loop (earth fault on one conductor, healthy conductor of the same length)
Rule note

At balance. P is the arm connected to the faulty conductor.

B · Conductor resistance (solid, low-resistance fault)
Rule note

Only for a solid fault. Fault and earth resistance add error. Not for an open circuit.

Rule note

Copper resistance is corrected back to 20 °C.

C · TDR (time-domain reflectometer)
Rule note

Placeholder. Take it from the cable datasheet or calibrate on a known length.

D · Capacitance (open circuit or break)
Rule note

Measured on a healthy conductor of the same cable, or nF per km from the datasheet × length.

4 · Half-split tracker

How it works

Open the circuit at a test point and test the section from the source to that point. If it is healthy, the fault is further out. If it is faulty, the fault is nearer the source. The tracker narrows the bracket and gives the next test point.

FAQ

AGL Fault Location Calculator (Advanced): Frequently Asked Questions

Quick answers on classifying a cable fault, estimating its distance and narrowing the search.

What does the AGL Fault Location Calculator (Advanced) do?

It classifies the fault, calculates a distance by Murray loop, conductor resistance, TDR or capacitance, narrows it with a half-split tracker, and combines every estimate into one search window along the circuit. Several methods that agree give a narrow, confident window. Every distance is measured from the same end of the circuit.

How is the fault classified?

You enter the insulation resistance to earth and the minimum acceptable value, the conductor continuity, and the CCR output voltage measured and expected. The fault type then decides which distance methods apply. The minimum insulation resistance is a placeholder, so use your specification.

Which method should I use for which fault?

For an earth (insulation) fault, use the Murray loop with a healthy conductor of the same length, TDR, or conductor resistance for a solid fault, then half-split. For an open circuit, use TDR or capacitance, then half-split. Murray and conductor resistance do not apply to an open circuit. For extra series resistance, half-split and then check joints and connectors in the bracketed section. For a missing load or shorted section, half-split the circuit and check lamps and transformers.

What formulas does it use for distance?

Murray loop: x = 2L times P divided by (P plus Q), where P is the ratio arm on the faulty side and Q is the healthy side. Conductor resistance: the resistance corrected to 20 degrees C divided by the resistance per metre. TDR: velocity of propagation times the round-trip echo time, divided by 2. Capacitance: cable length times the capacitance measured to the break, divided by the capacitance of the full length. In each case x is the distance from the test end.

How does the half-split tracker work?

Open the circuit at a test point and test the section from the source to that point. A healthy result moves the lower end of the bracket out to the test point, and a faulty result moves the upper end in. The tracker gives the next test point, and you repeat until the bracket is about one fixture spacing.

How is the combined search window and agreement worked out?

The window runs from the lowest to the highest estimate, padded by one fixture spacing or 1 percent of the circuit length, whichever is larger. The probable location is the average of all estimates, including the half-split mid-point once a result is recorded. Agreement is High when the spread is up to 5 percent of the circuit length, Medium up to 15 percent, and Low above 15 percent. With only one method it is shown as a single method.

Can you give a worked example?

On a 1,200 m circuit with Murray arms P = 300 and Q = 700, the distance is 2 x 1,200 x 300 / 1,000 = 720 m, about fixture 24 at 30 m spacing. Conductor resistance gives 720.8 m, TDR gives 697 m at 8.2 microseconds and 170 m per microsecond, and capacitance gives 700 m from 70 nF of 120 nF.

Is the result exact?

No. These calculations give an estimate, and cable route length, joints, bends and temperature all add error. Use the search window to dig or open the circuit at the marked fixture, and confirm with a retest. Always isolate and discharge the circuit before any work.

More Tools

Related Knowledge Hub Resources

Talk to Precision AGL Academy

Follow the Academy

Probable location (m)—