What are remote diagnostics?

Reading a CCR and its circuit from the control room — live values, trends and logs — so a problem is understood, and a site visit prepared, before anyone goes to the airfield.

REMOTE DIAGNOSTICS · FROM FIELD DATA TO A PREPARED VISIT 1 FIELD CCR AND FIELD UNIT DATA 2 LINK SECURE NETWORK TO THE CONTROL ROOM 3 ALCMS SHOWS VALUES, TRENDS AND LOG 4 ENGINEER ASSESSES AND PLANS THE VISIT READING IS LOW-RISK — ACTING NEEDS AUTHORITY AND A CONFIRMED-SAFE FIELD LIVE VALUES CURRENT, VOLTAGE, LOAD TEMPERATURE, LEAKAGE TRENDS & LOG HISTORY OF READINGS ALARMS AND EVENTS SETTINGS LIMITS, STEPS, MODE CHANGE UNDER CONTROL REMOTE ACTIONS COMMAND OR RESET ONLY WHEN FIELD IS SAFE KEY POINT REMOTE DIAGNOSTICS PREPARES THE FIELD VISIT — IT DOES NOT REPLACE IT SCHEMATIC · NOT TO SCALE
field data
link and live values
trends and planning
restricted actions
The Fact Diagnostics

Remote diagnostics means examining the lighting equipment from the control room instead of walking the airfield. The control system’s link to each CCR and field unit carries live values (current, voltage, load, temperature, earth leakage), trends, settings and the event log, so an engineer can see how the equipment is behaving, and how it has behaved, before going anywhere.

The strongest use is trends. A reading inside its limits looks healthy, but one that climbs steadily towards its limit, such as earth leakage or CCR temperature, shows a problem developing and can be planned for before it trips. The limits are just as important: remote data shows symptoms, not damage, so the cause is still confirmed on site. Remote actions are different from remote reading. A remote command or reset can energise a circuit, so it must never be sent unless the field is confirmed safe; local mode and isolation at the equipment protect anyone working there.

  1. Connect. Access the CCR or field unit through the control system, with the right authority.
  2. Read. Look at live values, then the trend and event log behind them.
  3. Assess. Decide what the pattern suggests and what only a site visit can confirm.
  4. Prepare. Plan the visit: what to check, which tools and spares, what to isolate.
  5. Act safely. Do anything that changes the equipment only when the field is confirmed safe.
WhatExamining CCRs and circuits from the control room
ReadsCurrent, voltage, load, temperature, leakage, step, mode, alarms, event log
BenefitFewer visits, faster first assessment, better-prepared visits
LimitCannot see physical damage; the cause is confirmed on site
NeedsSecure link, access control and authority for any action
ReferenceIEC 61820-3-2:2023 (CCRs) · FAA AC 150/5345-56 (L-890 ALCMS) · ICAO Doc 9157 Pt 5
General description only. Which data is available, how long history is kept, and what remote access or actions are allowed vary by CCR, field unit and control-system manufacturer and by the airport’s security and operating procedures.

Remote Diagnostics Explorer

Pick a circuit to examine remotely

Remote view LAST 30 DAYS

What it tells you NOT A DIAGNOSIS

Teaching simulation. Values and trends are illustrative, shown as a percentage of an alarm limit where noted. Real data, limits and history depend on the equipment and project design.

Entry 18 · Fault indication Entry 20 · Equipment status

Frequently Asked Questions

Q1What are remote diagnostics?

Examining the lighting equipment from a distance through the control system's link to the CCRs and field units. Engineers read live values, trends, settings and event logs without going to the airfield.

Q2What data can be read remotely?

Typically output current, output voltage, load, temperature, earth leakage, selected step, mode, alarms and the event log. Which items are available depends on the CCR, field unit and control system.

Q3What are the benefits?

Fewer unnecessary field visits, faster first assessment, and better-prepared visits where the engineer arrives knowing what to check and what parts or test equipment to bring. Trends can also show a developing fault before it causes an outage.

Q4What can remote diagnostics not do?

They cannot see physical problems such as a flooded base, a loose connector or a worn fixture. They show symptoms and trends, so the cause is still confirmed by testing and inspection on site.

Q5Is it safe to reset or switch a CCR remotely?

Only when the field is confirmed safe. A remote command can energise a circuit, so it must never be sent while anyone may be working on it. Isolation and lockout at the equipment, and the local or remote mode, protect people, and remote access needs authority and security controls. A remote off indication is not proof that a circuit is dead, so isolation is still proved at the equipment.

Q6Why do trends matter more than a single reading?

A single value inside its limits looks fine. A value that climbs steadily towards its limit, such as earth leakage or CCR temperature, shows a problem developing, which can be planned for before it trips.

Precision AGL Academy

See It. Understand It. Then Learn How to Engineer It.

Recognising an AGL system visually is the first step. The next step is knowing how to design, install, test, commission and maintain them correctly.

Build Practical AGL Engineering Skills

Go deeper with structured training from Precision AGL Academy, covering:

AGL Fundamentals Design & Electrical Engineering Approach Lighting Photometry Installation & Commissioning Maintenance & Troubleshooting

Learn how each light, sign and circuit works as part of a complete airport lighting system, not just as an isolated diagram.

See. Understand. Apply. Engineer.