How do you troubleshoot several fixtures failing at once?

One dark light points to the fixture. Several failing together point to the circuit, and the pattern of which lights are out shows what kind of circuit fault to look for.

MULTIPLE-FIXTURE FAILURE · SUSPECT THE CIRCUIT, NOT THE FIXTURECCRSHORT:BEYOND IT DARKSHORTCUTCCREVERY 2ND:ONE CIRCUIT OUT1PATTERNEVERY 2ND LIGHT DARKCause: one interleavedcircuit out: open / CCRCheck: CCR alarm, output2PATTERNBEYOND A POINT DARKCause: short circuitbypasses the loopCheck: IR / continuity, split3PATTERNSCATTERED LIGHTS DARKCause: common cause:water, surge, ageingCheck: pits, connectors, each4PATTERNSEVERAL DIM TOGETHERCause: step setting, leakageor heavy loadingCheck: CCR current at step5PATTERNEACH LOCAL FAULTCause: separate fixture-sidefaults, loop completeCheck: secondary, then fixtureTELL ATC · CCR OFF, ISOLATED, LOCKED OUT · PROVE DEAD & EARTH · THEN SPLIT THE LOOP AND TEST
lit fixture / series loop
interleaved circuit out
short circuit / safety
common cause / local
The Fact Multiple-fixture fault tracing

On a series circuit with isolation transformers the loop stays complete when one fixture fails, so one dark light points at the fixture. If several fixtures fail together, suspect the circuit, not the fixture. The pattern shows which fault. Every second light dark means one interleaved circuit is out, usually an open circuit or a CCR problem. Lights beyond a point dark while those before it stay lit suggests a short circuit that bypasses the rest of the loop, with the CCR seeing a smaller load. Scattered lights dark with the loop complete points to a common cause such as water in pits, connector faults, surge damage or ageing sources.

Several lights dim together points to the step setting, or to leakage or heavy loading that stops the CCR delivering its current, so the CCR output current is read first. ATC is told, the CCR is switched off, isolated and locked out, and the circuit is proved dead and earthed as the site procedure requires before anything is touched. The outage is reported (for example by NOTAM) as the authority requires. The loop is then split into sections and tested by continuity or insulation resistance. If the circuit and transformers are healthy, each affected fixture is checked on its own side: secondary, connector, then the fixture. After repair the circuit is retested and the findings recorded.

RuleSeveral together: suspect the circuit
Every second light darkOne interleaved circuit out
Beyond a point darkShort circuit bypass
Scattered dark, loop completeCommon cause
Several dimStep, leakage, loading
First actionTell ATC, isolate, prove dead, earth
Locate bySplit the loop, test sections
ReferenceICAO Annex 14 Vol I Ch 10; ICAO Doc 9137 Part 9; ICAO Doc 9157 Part 5; FAA AC 150/5340-26; manufacturer manuals and airport safe-working rules
Awareness schematic only, not a fault-finding procedure. Series circuits carry high current and can be lethal. Test methods, limits and isolation points come from the manufacturer, the standards and the airport’s safety procedures.
Entry 27 · Intermittent-fault troubleshooting Entry 29 · Snow and ice effects on inset lights

Frequently Asked Questions

Q1Why are several failed fixtures treated differently from one?

On a series circuit with isolation transformers the loop stays complete when one fixture fails, so one dark light points to the fixture side. If several fixtures fail together, the cause is suspected in the circuit, not in the fixtures.

Q2What does it mean if every second light is dark?

Lights in a zone are often interleaved across two circuits, so losing one circuit leaves every second light lit instead of a gap in the pattern. The dark lights are on the circuit that has failed, usually an open circuit or a CCR problem, found from the CCR alarm and output.

Q3What if the lights beyond a certain point are dark and the ones before it are lit?

That pattern suggests a short circuit. Current takes the shortcut and bypasses the rest of the loop, so fixtures before the short usually stay lit and those beyond it go dark. The CCR sees a smaller load and holds its current at a lower voltage.

Q4What if several scattered lights are dark but the loop is complete?

A common cause is likely rather than a break in the loop. Water in pits, connector faults, surge damage and ageing light sources are checked, and each affected fixture is then tested on its own side, starting with the secondary and the connector.

Q5Why would several lights be dim together?

Dim lights point to the brightness step setting, or to leakage or heavy loading that stops the CCR delivering its current. The CCR output current is read at the selected step before the fixtures are blamed.

Q6What is done before any fixture or circuit is touched?

ATC is told, the CCR is switched off, isolated and locked out, and the circuit is proved dead and earthed as the site procedure requires. The loop is then divided into sections and tested by continuity or insulation resistance. After repair the circuit is retested and the findings recorded.

Precision AGL Academy

See It. Understand It. Then Learn How to Engineer It.

Recognising an AGL system visually is the first step. The next step is knowing how to design, install, test, commission and maintain them correctly.

Build Practical AGL Engineering Skills

Go deeper with structured training from Precision AGL Academy, covering:

AGL Fundamentals Design & Electrical Engineering Approach Lighting Photometry Installation & Commissioning Maintenance & Troubleshooting

Learn how each light, sign and circuit works as part of a complete airport lighting system, not just as an isolated diagram.

See. Understand. Apply. Engineer.