How do you troubleshoot an earth fault?

An earth fault is silent until it is detected, so the work runs in order: spot the alarm or the falling reading, make the circuit safe, then split the loop and test each section until one is left.

EARTH-FAULT TROUBLESHOOTING · DETECT, ISOLATE, LOCATECCRloop outPIT 1SECTION 1PIT 2SECTION 2PIT 3SECTION 3PIT 4LOOP RETURNS TO CCRLEAK TO EARTHWET CONNECTOR OR DAMAGED CABLESINGLE FAULT: LOOP STAYS CLOSED, LIGHTS USUALLY STAY ON1SYMPTOMEARTH-FAULT ALARMCause: current leaking toearth in the loopCheck: CCR code, isolate2SYMPTOMLIGHTS ON, IR FALLINGCause: silent single fault:moisture, damage, ageCheck: trend vs baseline3SYMPTOMSECTION DARK, LOOP ONCause: second fault canbypass a sectionCheck: continuity, IR by section4SYMPTOMLOW IR, FAULT UNKNOWNCause: leak somewherein the loopCheck: half-split at pits5WHERE TO LOOKLIKELY SITESWet connectors, joints,cable, transformer primaryCheck: after works firstTELL ATC · CCR OFF, ISOLATED, LOCKED OUT · PROVE DEAD · TREAT AS A SAFETY ISSUE
series loop
silent / trending
leak to earth / safety
locate / likely sites
The Fact Earth-fault tracing

An earth fault is an unintended path between the series loop and earth, caused by failed insulation on a cable, connector or transformer primary. A series circuit is not referenced to earth, so a single fault does not break the loop: the lights usually stay on and the fault can go unnoticed without testing or monitoring. It shows as a CCR earth-fault alarm or trip, or as insulation resistance that falls from test to test, often well before any alarm. A second fault elsewhere can give current a path through the ground and bypass the section between the two faults.

Faulted insulation can put voltage on metalwork or the ground nearby, so a suspected earth fault is a safety issue. ATC and airport operations are told so the outage can be agreed, the CCR code and readings are noted before any reset, and the CCR is switched off, isolated, locked out and tagged, with the circuit proved dead. The loop is then divided at accessible points such as pits and tested by insulation resistance using the half-split: test about half, set the good half aside, split the bad half again until one section or device remains. The circuit is discharged after each insulation test, since cable holds charge. Wet connectors, joints and terminations, damaged cable and degraded transformer primaries are the usual sites, and areas disturbed by works are checked first. After repair the section and the whole circuit are retested and the readings recorded.

Single faultLoop closed, lights usually on
Second faultCan bypass the section between
IndicationCCR alarm, falling IR
Locate byInsulation test, half-split
Typical causesWet joint, damaged cable
First actionTell ATC, isolate, prove dead
After repairRetest, restore, record
ReferenceICAO Doc 9157 Part 5; FAA AC 150/5340-26; manufacturer manuals and airport safe-working rules
Awareness schematic only, not a fault-finding procedure. Series circuits carry high current and can be lethal. Test voltage, duration, minimum readings and isolation points come from the manufacturer, the standards and the airport’s safety procedures.
Entry 25 · ALCMS troubleshooting Entry 27 · Intermittent-fault troubleshooting

Frequently Asked Questions

Q1What is an earth fault in a series lighting circuit?

An unintended path between the series loop and earth, caused by failed insulation on a cable, connector or transformer primary. Because the circuit is not referenced to earth, a single leak does not break the loop, so the lights usually stay on and the fault can go unnoticed without testing or monitoring.

Q2Why is a single earth fault still taken seriously?

A second earth fault elsewhere can give current a path through the ground, bypassing the section between the two faults, much like a short circuit. Faulted insulation can also put voltage on metalwork or the ground nearby, so a suspected earth fault is a safety issue.

Q3What is done first when an earth-fault alarm or CCR trip appears?

ATC and airport operations are told so the outage can be agreed, the code and readings are noted before any reset, and the CCR is switched off, isolated, locked out and tagged. The circuit is proved dead before anyone touches it.

Q4How is the fault located?

By insulation resistance and the half-split method. The loop is divided at accessible points such as pits, about half is tested, the good half is set aside, and the bad half is split again until one section or device remains. The circuit is discharged after each insulation test, since cable holds charge.

Q5Where do earth faults most often occur?

At made-up seals and places that suffer water or damage: wet connectors, cable joints and terminations, damaged cable, and transformer primaries with degraded insulation. Areas disturbed by excavation or work at a crossing or duct are checked first.

Q6What happens after the repair?

The repaired section and then the whole circuit are retested for insulation resistance, the CCR is restored and status confirmed, and the readings are recorded as a new baseline. A low reading, or one that keeps falling, is trended because it often appears well before a fault.

Precision AGL Academy

See It. Understand It. Then Learn How to Engineer It.

Recognising an AGL system visually is the first step. The next step is knowing how to design, install, test, commission and maintain them correctly.

Build Practical AGL Engineering Skills

Go deeper with structured training from Precision AGL Academy, covering:

AGL Fundamentals Design & Electrical Engineering Approach Lighting Photometry Installation & Commissioning Maintenance & Troubleshooting

Learn how each light, sign and circuit works as part of a complete airport lighting system, not just as an isolated diagram.

See. Understand. Apply. Engineer.